Rockwell Automation Logix5000 Systems: Connecting PowerFlex 40 Drives over an EtherNet/IP Network Quick Start User Manual
Page 30
30
Rockwell Automation Publication IASIMP-QS029A-EN-P - February 2012
Chapter 2 Add the PowerFlex 40 Drive to an RSLogix 5000 Project
2.
To change drive parameters, click
the Value column cell for the
parameter and make a change.
Some Value cells use pull-down
menus and others allow you to
type a different value.
For example, parameter 41 Reset
to Defalts can be changed to Factory Rset to revert all parameters to the default values for
the drive.
3.
Change the following parameters to the following values:
•
P036 = Comm Port
•
P038 = Comm Port
Changing these parameter values gives you the option to control these functions from the
RSLogix 5000 software tags.
4.
Click Close.
5.
If required, upload parameters from the device.
IMPORTANT
The drive is reset and fault F048 is displayed and blinks. Press
on the touchpad to clear the fault.