Chapter 2 Add the PowerFlex 40 Drive to an RSLogix 5000 Project

5.

After the drive has reached 1.0
Hz, change the O.Start tag to 0.

6.

Change the O.Stop tag to 1.

The drive begins to slow until
reaching 0.0 Hz.

7.

When the drive reaches 0.0 Hz,
enter 0 at the O.Stop tag.

8.

Choose Go Offline.

By starting and stopping the drive, you verified the following conditions exist in
your application:

The controller is correctly communicating with the drive.

The drive can receive simple commands.