Dry fertilizer fan adjustment, A33 a14 – Great Plains 1625AHL Operator Manual User Manual

Page 59

Advertising
background image

Great Plains Manufacturing, Inc.

Table of Contents

Index

Operating Instructions

55

2014-04-21

Table of Contents

Index

411-020M

Dry Fertilizer Fan Adjustment
Refer to Figure 43
through Figure 44
1625AHD models have a third Magnehelic

®

gauge

,

with a fan system decal (right wing, inboard of Air-Pro

®

gauge

). This gauge has a scale of 0-to-50 inches of

water pressure. Typical readings are in the 35-45 range.

This gauge reads pressure inside the fan manifold

.

The manifold supplies air to both the seed meters (meter
pressurization air) and to the dry fertilizer meter.
Approximately 10% of the air is tapped at the top end of
the manifold for meter pressurization air. The tap fraction
is controlled by a butterfly valve, which has an initial
factory setting of approximately 75

°.

Use the tractor remote lever to set fan speed. Use the
butterfly valve adjustment to adjust air fraction for seed
and fertilizer metering. The objective is to obtain
sufficient pressure to avoid dry fertilizer blockage, and
sufficient seed meter pressure to avoid seeding skips
during end-of-pass marker fold, lift and turn.

Adjustments may be required for different field speeds,
different fertilizer rates or fertilizer composition. For initial
static (parked, no material flow) setup:

1.

Look up the recommended meter pressurization for
the intended crop (see Seed Rate manual). Make a
note of the previous or factory settings of all butterfly
valves. Load seed in hoppers and meters. Meters
must be full to inlet shutters for valid readings.

2.

Close the manifold outlet butterfly valve
(set to 90

°). If the wing butterfly valves have been

previously adjusted for balance, leave them
undisturbed, otherwise set them full open (0

°).

3.

For setup, operate the tractor engine at typical field
rpms, and not at idle. Run the fan at maximum oil
flow without over-speeding.

4.

Adjust manifold outlet butterfly valve

to achieve

recommended pressure on the Air-Pro

®

gauges

.

5.

Re-check both pressures

in the field, with

material flowing at desired rates. Adjust fan speed to
stay within 35 to 45 inches. Adjust the manifold outlet
butterfly valve

to the suggested pressure for the

seed.

Check all pressure early in the first pass, with fertilizer
flowing and seed disk pockets full. Adjust fan speed as
necessary. Stop and adjust butterfly valves as needed to
keep gauges in the desired range.

When planting and applying, check the seed monitor for
skip/double and fertilizer blockage alarms. Check gauge
pressures with full meters and at field speed. Adjust the
fan rpm to compensate for average pressure shifts.
Re-adjust the manifold outlet butterfly valve

for

optimal meter pressurization.

Note: Fan speed and manifold pressures changes

between application and no-fertilizer-metering
states. Monitor fan rpm, meter pressurization,
fertilizer blockage detection and fan pressure
gauge during application and turns.

Note: Fan rpm is dependent on back-pressure due to

material flow. Fan speed increases when flowing
material, due to cavitation.

Figure 43

Fertilizer Manifold (Fan) Gauge

31187

858-193C

36134

A33

A14

0

10

30

20

40

50

858-193C

A14

A33

D29

A15

Figure 44

Fertilizer Manifold Butterfly Valve

36134

858-208C

D29

A16

A11

A15

A15

A33

A14

A15

A15

Advertising
This manual is related to the following products: