Analog Input/Output Installation and Configuration 8-15

8. Connect +24VDC from the loop power supply to the blue and

brown wires (for Alpha cable) or to the blue and yellow wires
(for Belden cable).

9. Connect the power supply ground to the black wires that were

twisted with the blue/brown (Belden) or blue/yellow (Alpha)
pairs.

10. Activate the monitor with the monitoring point and analog

output configuration.

11. Using the Analog Output Diagnostic tools in Profile, manually

drive the outputs to 4, 12, and 20mA and confirm that each
channel is the correct value at the receiving instrument.

12. Return the monitor to normal mode, and confirm outputs are

changing and roughly match actual values.