Installation

3

Remove the knock-out hole in the terminal block cover for the input conduit. The hole must

accommodate 1” or 1.5” (25.4 mm or 38.1 mm) Intermediate Metal Conduit (IMC).

4

Pull the input wire through the conduit, leaving approximately 2 ft (0.5m) of exposed wire. Attach

a flexible metal fitting to the end of the conduit.

5

Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.

Strip 0.5” (1.5 cm) of insulation from the end of each incoming wire.

CAUTION:

If the UPS does not have an automatic protection device against current backfeed, install an

external isolating device (see Figure 21). After the device is installed, you must add a warning label with the
following wording or the equivalent on the external AC contactor: RISK OF VOLTAGE BACKFEED. Isolate the
UPS before operating on this circuit, then check for hazardous voltage between all terminals.

External Distribution Panel

UPS

L/L1

L/L1

N/L2

N/L2

Legend

Coil Remote Switch
Magneto-Thermal Input Main Switch
AC Contactor ( see Table 1)
Neutral/L2
L1 Line Input

B
Q

T
N/L2
L/L1

B

Q

T

Figure 21. Typical External Isolating Device Installation