Ups shutdown, Control panel functions – Dell UPS 10000R User Manual

Page 39

Advertising
background image

39

Operation

|

NOTE:

The UPS does not assume the load if you press the

button less than three seconds.

2

Press the button to check for active alarms or notices.

Ignore the “UPS on Battery” notice and notices that indicate missing utility power. Resolve other

active alarms before continuing. See “Troubleshooting” on page 84. After correcting the alarms,

restart if necessary.

You can prevent a battery start (requiring utility power at the next startup) by simultaneously pressing

the and buttons for three seconds. To disable the battery start, see the Start on Battery setting on

page 50.

UPS Shutdown

To shut down the UPS:

NOTE:

If devices are connected, prepare them to be shut down.

1

Press the

button on the front panel for three seconds.

The UPS begins to beep. The UPS transfers to Standby mode.

NOTE:

Releasing the

button before three seconds returns the UPS to its original operating state.

2

Switch off utility power where the UPS is connected.

After utility power is removed, the UPS fully shuts down in ten seconds.

Control Panel Functions

The UPS has a three-button graphical LCD. There are three buttons on the control panel:

S

Scroll up or back

S

Select

S

Scroll down or forward

Scroll Button
(Down or Forward)

Select Button

Scroll Button

(Up or Back)

Figure 28. UPS LCD Panel Controls