Safety warnings – Dell UPS 10000R User Manual

Page 9

Advertising
background image

9

Safety Warnings

|

Safety Warnings

CAUTION:

Before performing the procedures in this document, read and follow the safety instructions and

important regulatory information in your Safety, Environmental, and Regulatory Information document.

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS

This manual contains important instructions that you should follow during installation and

maintenance of the UPS and batteries. Please read all instructions before operating the equipment and

save this manual for future reference.

DANGER:

Observe the following instruction to help prevent an imminently hazardous situation which, if not

avoided, will result in death or serious injury:

S

The UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE
PARTS
inside the UPS or EBM.

WARNING:

Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall

perform the electrical installation.

WARNING:

Observe the following instructions to help prevent a potentially hazardous situation which, if not

avoided, could result in death or injury:

S

The UPS outputs are protected against overcurrent by circuit breakers.

S

This UPS contains its own energy source (batteries). The output receptacles may carry live voltage

even when the UPS is not connected to an AC supply.

S

To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent

protection with an ampere rating in accordance with the National Electrical Code

®

(NEC

®

),

ANSI/NFPA 70 or your local electrical code:

UPS Output Power

200V

208V

230V

10 kW

63A (Europe) and 80A (North America and Japan)

2-pole circuit breaker

S

To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity

controlled, indoor environment, free of conductive contaminants. Ambient temperature must not

exceed 40

°

C (104

°

F). Do not operate near water or excessive humidity (95% maximum).

S

Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and

on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely

dry (hazard of electric shock).

2

Advertising