Event log – Dell UPS 10000R User Manual

Page 45

Advertising
background image

45

Operation

|

Table 5. Battery Operating Status Notifications

Battery Status Notifications

Description

Battery charging

Batteries are charged in constant current mode.

Battery floating

Batteries are charged in constant voltage mode.

Battery resting

Batteries are connected but are not being charged or discharged.
(This is part of the normal charging cycle.)

Battery discharging

Batteries are discharging.

Battery disconnected

Batteries are unavailable because they are disconnected.

Charger disabled

The charger is off. You can enable the Charger setting from the Settings menu

(see page 52).

Event Log

The Event Log holds up to 50 events. You can scroll through the event screens, beginning with the most

recent event.

NOTE:

The date format depends on the language selection.

The first row of each event screen contains the date (MM/DD/YYYY) and time (hh:mm:ss) at which the

event occurred. The second row contains the type of event and code. The event description begins on

the third row and may continue to the fourth row. The bottom right corner of the event screen displays

two numbers: an ordering number of the event in the log, followed by the total number of events in the

log.

If there are no events in the log, the event status summary screen displays “No events in log.”

See “Retrieving the Event Log” on page 56.