Ups initial startup – Dell UPS 10000R User Manual

Page 32

Advertising
background image

32

|

Installation

Table 2. UPS Wiring Specifications

Wire Function

Terminal

Position

UPS Wire Function

Terminal Wire

Size Rating*

Tightening Torque

Input

1

Input Ground

16–35 mm

2

(8–2 AWG)

1.7 Nm (15 lb-in)

2

L2/Neutral In

3

L1 In

* Use a minimum:

S 10 mm

2 (

8 AWG) for equipment grounding wire, 75_C copper wire minimum

S 25 mm

2 (

4 AWG) for input line and neutral wires, 75_C copper wire minimum

7

Replace the terminal block cover.

8

Continue to the following section, “UPS Initial Startup.”

UPS Initial Startup

On/Off Button

LCD Panel

Scroll Button (Down or Forward)

Select Button

Scroll Button (Up or Back)

Figure 23. Starting the UPS

Advertising