Recharging and replacing batteries – Dell UPS 10000R User Manual

Page 71

Advertising
background image

71

UPS Maintenance

|

6

Replace the UPS front cover (see Figure 37).

Align the front cover with the front of the chassis.

Insert the right-side tabs on the front cover into the right-side chassis tab openings.

Push the left side of the cover forward and snap it to the chassis.

NOTE:

Ensure that the LCD panel on the UPS chassis aligns with the LCD window on the front cover before

securing the cover to the chassis.

1

2

Figure 37. Replacing the UPS Front Cover

Recharging and Replacing Batteries

If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to

utility power. The batteries charge to 90% capacity in approximately 4 hours. However, it is

recommended that the batteries charge for 48 hours after long-term storage.

You should track recharge dates. Log the last date the batteries were recharged. Do not use the UPS if

the last recharge date was more than six months ago.

When the status summary screen displays the UPS fault icon with the “Service Battery” alarm and the

audible alarm sounds continuously, the batteries may need replacing.

Contact your service representative to order new batteries.

Advertising