Control screens – Dell UPS 10000R User Manual

Page 47

Advertising
background image

47

Operation

|

Control Screens

Table 6 describes the available control screens.

Table 6. Control Screens

Control Screens

Description

Go to Bypass

Transfers the UPS system to internal Bypass mode.
When the Go to Bypass command is issued, the screen immediately shows the

message for five seconds: Manual Bypass Command. The option then changes to

Go to Normal.
When the Go to Normal command is issued, the screen immediately shows the

message Normal Mode Command Sent for five seconds. The option then changes

to Go to Bypass.

Battery Test

Schedule Battery Test: yes | Cancel Battery test: no
Starts a manual battery test.
See “Testing Batteries” on page 78.

Reset Error State

Reset Alarms: yes | no
Manually clears any latched alarms, such as bad battery detected, overload, or DC

Bus OV/UV.
If a bad battery alarm was also active, reset the battery test status to “Not

Tested.”

Load Segments

Load segment 1: on | off
Load segment 2: on | off
These on/off commands override automatic load segment on/off controls made by

the Automatic Start Delay and Automatic On Battery Shutdown settings. See

“Configuring Load Segments” on page 57.

Restore Factory Settings

Restore Factory Settings: yes | no
Available only in Standby mode.
Restoring the factory settings:

S Returns all user-configurable EEPROM settings to default factory settings
S Resets all pending on/off commands
S Clears the Event Log and resets all time stamps
S Resets the battery test status
S Initiates the Self Diagnostics test