Configuring battery settings, Configuring the ups for an ebm – Dell UPS 10000R User Manual

Page 60

Advertising
background image

60

|

Operation

Configuring Battery Settings

Configure the UPS settings for an installed EBM, including whether to run automatic battery tests and

automatic restart configuration.

Configuring the UPS for an EBM

If the UPS is not configured for the EBM, the UPS reports less battery time remaining on the UPS front

panel and to any remote software. You may receive a shutdown warning prematurely. To ensure

maximum battery runtime when using power management software, configure the UPS for the EBM:

1

Press the

button for longer than one second to go to the main menu selection and scroll down to

the Settings menu using the button.

2

Press the button to enter the Settings menu.

3

Use the button to scroll to the External Battery Modules option and press the button.

The battery number value begins to flash.

4

Set the battery number value using the and buttons.

Configuration

Setting

UPS only (internal batteries)

0 (default)

UPS + 1 EBM

1

NOTE:

Runtime is automatically adjusted based on present load levels and whether an EBM is configured.

NOTE:

This value represents to the number of attached EBM units, not the number of battery strings.

5

Press the button to confirm.