Configure outlet settings and the outlet name, User’s guide – Dell Managed PDU LED User Manual
Page 115
USER’S GUIDE
Ma
na
ge
d R
a
ck
PD
U
110
Configure outlet settings and the outlet name
T
he following settings are available:
Setting
Description
Name
Set the name for one or more outlets. The name is displayed next
to the outlet number on status screens.
External Link
Define an HTTP or HTTPS link to a Web site or IP address.
•
•
http://pdu_ip_address
, where
pdu_ip_address
is the IP
address of the Rack PDU and links the outlet to the Web interface
of the Rack PDU at the IP address, enabling authorized users to
log on.
Power On Delay
Set the number of seconds that the Rack PDU waits after a
command is issued before applying power from an outlet.
N
OTE
:
To configure an outlet to remain off at all times, check the
Never
checkbox next to
Power On Delay
.
Power Off Delay
Set the number of seconds that the Rack PDU waits after a
command is issued before removing power from an outlet.
N
OTE
:
To configure an outlet to remain on at all times, check the
Never
check box next to
Power Off Delay
.
Reboot Duration
Set the number of seconds an outlet remains off before restarting.