Description:
Set or view the overload restriction feature to prevent outlets from turning
on when the overload alarm threshold is violated. Acceptable arguments are none,
near
, and over. To specify phases, choose from the following options. Type: all, a
single phase, a range, or a comma-separated list of phases.
Example 1:
To set the overload restriction for phase three to none, type:
cli> phRestrictn 3 none
E000: Success
Example 2:
To view the overload restrictions for all phases, type:
cli> phRestrictn all
E000: Success
1: over
2: near
3: none