Phrestrictn, User’s guide – Dell Managed PDU LED User Manual

Page 81

Advertising
background image

USER’S GUIDE

Ma

na

ge

d R

a

ck

PD

U

76

phRestrictn

Access:

Administrator

Description:

Set or view the overload restriction feature to prevent outlets from turning

on when the overload alarm threshold is violated. Acceptable arguments are none,
near

, and over. To specify phases, choose from the following options. Type: all, a

single phase, a range, or a comma-separated list of phases.

Example 1:

To set the overload restriction for phase three to none, type:

cli> phRestrictn 3 none

E000: Success

Example 2:

To view the overload restrictions for all phases, type:

cli> phRestrictn all

E000: Success

1: over

2: near

3: none

Advertising