Olnearover, User’s guide – Dell Managed PDU LED User Manual
Page 66

USER’S GUIDE
Ma
na
ge
d R
a
ck
PD
U
61
olNearOver
Access:
Administrator, Device User, and Outlet User, but only for outlets to which the
user is assigned.
Description:
Set or view the outlet near overload warning threshold.
Example 1:
To view the near overload threshold for outlets 3 and 5 through 7, type:
cli> olNearOver 3,5-7
E000: Success
3: BobbysServer: 5 W
5: BillysServer: 6 W
6: JoesServer: 5 W
7: JacksServer: 4 W
Example 2:
To set the near overload threshold for outlets 3 and 5 through 7 to
six watts, type:
cli> olNearOver 3,5-7 6
E000: Success
3: BobbysServer: 6 W
5: BillysServer: 6 W
6: JoesServer: 6 W
7: JacksServer: 6 W
Argument
Description
all
All device outlets.
<outlet
name>
The name configured for a specific outlet. (See
<outlet#>
A single number or a range of numbers separated with a
dash, or a comma-separated list of single outlet numbers
and number ranges.
<power>
The new outlet threshold (watts).