Dell PowerEdge C6100 User Manual
Page 46
![background image](/manuals/621780/46/background.png)
46
Using the Baseboard Management Controller
Table 1-48. Threshold Settings and Converting Formulas
Sensor
Number
Sensor Name
The Converting Formula
Upper non-
recoverable
Upper
critical
Upper
non-critical
Lower non-
recoverable
Lower
critical
Lower
non-critical
52h
VCORE 2
Actual_Reading (Volts) = Raw_Data x 0.0116
0xFF
0xFF
0xFF
0x00
0x00
0x00
Temperature
21h
MLB TEMP 1
Actual_Reading (degrees C) = Raw_Data
0x5A
0x57
0x55
0x00
0x00
0x00
22h
MLB TEMP 2
Actual_Reading (degrees C) = Raw_Data
0x5A
0x57
0x55
0x00
0x00
0x00
23h
MLB TEMP 3
Actual_Reading (degrees C) = Raw_Data
0x5A
0x57
0x55
0x00
0x00
0x00
61h
Processor 1 Temp Actual_Reading (degrees C) = Raw_Data
0x5A
0x55
0x51
0x00
0x00
0x00
62h
Processor Temp 2 Actual_Reading (degrees C) = Raw_Data
0x5A
0x55
0x51
0x00
0x00
0x00
2Ah
FCB Ambient1 Actual_Reading (degrees C) = Raw_Data
0xFF
0x32
0x00
0x00
0x00
0x00
2Bh
FCB Ambient2 Actual_Reading (degrees C) = Raw_Data
0xFF
0x32
0x00
0x00
0x00
0x00