Dell PowerVault NX3500 User Manual

Page 25

Advertising
background image

About Your Solution

25

E1311

Fan module ##

RPM exceeding

range. Check

fan.

RPM of specified fan in

specified module is

outside of intended

operating range.

See "Troubleshooting

System Cooling

Problems" on page 96.

E1313

Fan redundancy

lost. Check

fans.

The system is no longer

fan redundant. Another

fan failure would put the

system at risk of

over-heating.

Check LCD for

additional scrolling

messages. See

"Troubleshooting a Fan"

on page 97.

E1410

Internal Error

detected.

Check "FRU X".

Specified processor has an

internal error. The error

may or may not have been

caused by the processor.

Remove AC power to the

system for 10 seconds and

restart the system.
If the problem persists,

see "Getting Help" on

page 113.

E1414

CPU # temp

exceeding

range. Check

CPU heatsink.

Specified processor is out

of acceptable temperature

range.

Ensure that the processor

heat sink is properly

installed. See

"Troubleshooting the

Processor" on page 102

and "Troubleshooting

System Cooling

Problems" on page 96.

E1418

CPU # not

detected.

Check CPU is

seated

properly.

Specified processor is

missing or bad, and the

system is in an

unsupported

configuration.

Ensure that the specified

microprocessor is

properly installed. See

"Troubleshooting the

Processor" on page 102.

E141C

Unsupported

CPU

configuration.

Check CPU or

BIOS revision.

Processor is in an

unsupported

configuration.

Ensure that your

processor matches and

conforms to the type

described in the processor

technical specifications

outlined in your system’s

Getting Started Guide.

Table 1-3. LCD Status Messages

(continued)

Code

Text

Causes

Corrective Actions