19XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Starter Type
(0=Full, 1=Red, 2=SS/VFD)

0 to 2

1

Motor Rated Line Voltage

200 to 13200

VOLTS

460

Volt Transformer Ratio: 1

1 to 35

1

Overvoltage Threshold

105 to 115

%

115

Undervoltage Threshold

85 to 95

%

85

Over/Under Volt Time

1 to 10

SEC

5

Voltage% Imbalance

1 to 10

%

10

Voltage Imbalance Time

1 to 10

SEC

5

Motor Rated Load Amps

10 to 5000

AMPS

200

Motor Locked Rotor Trip

100 to 60000

AMPS

1000

Locked Rotor Start Delay

1 to 10

cycles

5

Starter LRA Rating

100 to 60000

AMPS

2000

Motor Current CT Ratio: 1

3 to 1000

100

Current% Imbalance

5 to 40

%

15

Current Imbalance Time

1 to 10

SEC

5

Grnd Fault CT’s?

0/1

NO/YES

YES

Ground Fault CT Ratio: 1

150

150

Ground Fault Current

1 to 25

AMPS

15

Ground Fault Start Delay

1 to 20

cycles

10

Ground Fault Persistence

1 to 10

cycles

5

Single Cycle Dropout

0/1

DSABLE/ENABLE

DSABLE

Frequency-60 Hz? (No=50)

0/1

NO/YES

YES

Line Frequency Faulting

0/1

DSABLE/ENABLE

DSABLE