Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 23

Advertising
background image

23

Table 2 — CVC/ICVC Display Data (cont)

EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press

(

will be highlighted).

3. Press .

NOTES:
1. Reset, Off, Local, CCN
2. Timeout, Ready, Recycle, Prestart, Start-up, Ramping, Running, Demand, Override, Shutdown, Trippout, Pumpdown, Lockout
3. Normal, Alert, Alarm
4. All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN

devices.

EXAMPLE 3 — STARTUP DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press

.

2. Press .
3. Scroll down to highlight

.

4. Press .

NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write
operations for the CVC/ICVC only.

DESCRIPTION

STATUS

UNITS

POINT

Control Mode

NOTE 1

NOTE 1

MODE

Run Status

NOTE 2

NOTE 2

STATUS

Start Inhibit Timer

0-15

min

T_START

Occupied?

0/1

NO/YES

OCC

System Alert/Alarm

0-2

NOTE 3

SYS_ALM

*Chiller Start/Stop

0/1

STOP/START

CHIL_S_S

*Remote Start Contact

0/1

OPEN/CLOSE

REMCON

Temperature Reset

–30-30

DEG F

T_RESET

*Control Point

10-120

DEG F

LCW_STPT

Chilled Water Temp

–40-245

DEG F

CHW_TMP

*Active Demand Limit

40-100

%

DEM_LIM

Average Line Current

0-999

%

%_AMPS

Motor Percent Kilowatts

0-999

%

KW_P

Auto Demand Limit Input

4-20

mA

AUTODEM

Auto Chilled Water Reset

4-20

mA

AUTORES

Remote Reset Sensor

–40-245

DEG F

R_RESET

Total Compressor Starts

0-99999

c_starts

Starts in 12 Hours

0-8

STARTS

Compressor Ontime

0-500000.0

HOURS

c_hrs

*Service Ontime

0-32767

HOURS

S_HRS

Ice Build Contact

0-1

OPEN/CLOSE

ICE_CON

Refrigerant Leak Sensor

0-20

mA

REF_LEAK

DESCRIPTION

STATUS

UNITS

POINT

Actual Guide Vane Pos

0-100

%

GV_ACT

**Chilled Water Pump

0-1

OFF/ON

CHWP

Chilled Water Flow

0-1

NO/YES

CHW_FLOW

**Condenser Water Pump

0-1

OFF/ON

CDP

Condenser Water Flow

0-1

NO/YES

CDW_FLOW

Oil Pump Relay

0-1

OFF/ON

OILR

**Oil Pump Delta P

–6.7-200

^PSI

OILPD

Compressor Start Relay

0-1

OFF/ON

CMPR

Compressor Start Contact

0-1

OPEN/CLOSED

CR_AUX

Starter Trans Relay

0-1

OFF/ON

CMPTRANS

Compressor Run Contact

0-1

OPEN/CLOSED

RUN_AUX

**Tower Fan Relay Low

0-1

OFF/ON

TFR_LOW

**Tower Fan Relay High

0-1

OFF/ON

TFR_HIGH

Starter Fault

0-1

ALARM/NORMAL

STR_FLT

Spare Safety Input

0-1

ALARM/NORMAL

SAFETY

Shunt Trip Relay

0-1

OFF/ON

TRIPR

ISM Fault Status

0-255

STRSTAT

MENU

STATUS

MAINSTAT

SELECT

MENU

STATUS

STARTUP

SELECT

Advertising