Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 22

Advertising
background image

22

Table 2 — CVC/ICVC Display Data

1. Only 12 lines of information appear on the chiller display screen

at any one time. Press the

or

softkey to

highlight a point or to view items below or above the current

screen. Press the

softkey twice to page forward; press

the

softkey twice to page back.

2. To access the information shown in Examples 10 through 22,

enter your 4-digit password after pressing the

soft-

key. If no softkeys are pressed for 15 minutes, the CVC/ICVC

automatically logs off (to prevent unrestricted access to PIC II
controls) and reverts to the default screen. If this happens, you

must re-enter your password to access the tables shown in

Examples 10 through 22.

3. Terms in the Description column of these tables are listed as they

appear on the chiller display screen.

4. The CVC/ICVC may be configured in English or Metric (SI) units

using the CVC/ICVC CONFIGURATION screen. See the Service
Operation section, page 45, for instructions on making this
change.

5. The items in the Reference Point Name column do not appear on

the chiller display screen. They are data or variable names used
in CCN or Building Supervisor (BS) software. They are listed in
these tables as a convenience to the operator if it is necessary to
cross reference CCN/BS documentation or use CCN/BS pro-
grams. For more information, see the 19XR CCN literature.

6. Reference Point Names shown in these tables in all capital let-

ters can be read by CCN and BS software. Of these capitalized
names, those preceded by a dagger can also be changed (that
is, written to) by the CCN, BS, and the CVC/ICVC. Capitalized
Reference Point Names preceded by two asterisks can be
changed only from the CVC/ICVC. Reference Point Names in
lower case type can be viewed by CCN or BS only by viewing the
whole table.

7. Alarms and Alerts: An asterisk in the far right field of a CVC/

ICVC status screen indicates that the chiller is in an alarm state;
an exclamation point in the far right field of the CVC/ICVC screen
indicates an alert state. The asterisk (or exclamation point) indi-
cates that the value on that line has exceeded (or is approach-
ing) a limit. For more information on alarms and alerts, see the
Alarms and Alerts section, page 15.

LEGEND

EXAMPLE 1 — CHILLER DISPLAY DEFAULT SCREEN

The following data is displayed in the Default screen.

NOTE: The last three entries are used to indicate operating mode to the PIC II. These values may be forced by the CVC/ICVC only.

IMPORTANT: The following notes apply to all Table 2
examples.

NEXT

PREVIOUS

NEXT

PREVIOUS

SERVICE

CCN

Carrier Comfort Network

CHW

Chilled Water

CHWR — Chilled Water Return
CHWS — Chilled Water Supply
CVC

Chiller Visual Controller

CT

Current Transformer

ECW

Entering Chilled Water

HGBP

Hot Gas Bypass

ICVC

International Chiller Visual Controller

ISM

Integrated Starter Module

LCW

Leaving Chilled Water

LRA

Locked Rotor Amps

mA

Milliamps

P

Pressure

PIC II

Product Integrated Controls II

SS

Solid State

T

Temperature

VFD

Variable Frequency Drive

WSM

Water System Manager

DESCRIPTION

STATUS

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

DISPLAY

(PRIMARY MESSAGE)
(SECONDARY MESSAGE)
(DATE AND TIME)

Compressor Ontime

0-500000.0

HOURS

C_HRS

Entering Chilled Water

–40-245

DEG F

ECW

CHW IN

Leaving Chilled Water

–40-245

DEG F

LCW

CHW OUT

Evaporator Temperature

–40-245

DEG F

ERT

EVAP REF

Entering Condenser Water

–40-245

DEG F

ECDW

CDW IN

Leaving Condenser Water

–40-245

DEG F

LCDW

CDW OUT

Condenser Temperature

–40-245

DEG F

CRT

COND REF

Oil Pressure

0-420

PSI

OILPD

OILPRESS

Oil Sump Temp

40-245

DEG F

OILT

OIL TEMP

Average Line Current

0-999

%

AMPS_%

AMPS%

0-1

CCN

0-1

LOCAL

0-1

RESET