Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 32

Advertising
background image

32

Table 2 — CVC/ICVC Display Data (cont)

EXAMPLE 21 — RAMP_DEM DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press

.

2. Press .

3. Scroll down to highlight

.

4. Press .
5. Scroll down to highlight

.

6. Press .

NOTE: No variables are available for CCN read or write operation.

EXAMPLE 22 — TEMP_CTL DISPLAY SCREEN

To access this display from the CVC/ICVC default screen:

1. Press .

2. Press .

3. Scroll down to highlight

.

4. Press .
5. Scroll down to highlight

.

6. Press .

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Pulldown Ramp Type:

0/1

ramp_opt

1

Select: Temp=0, Load=1

Demand Limit + kW Ramp

Demand Limit Source

0/1

dem_src

0

Select: Amps=0, kW=1
Motor Load Ramp% Min

5-20

kw_ramp

10

Demand Limit Prop Band

3-15

%

dem_prop

10

Demand Limit At 20 mA

40-100

%

dem_20ma

40

20 mA Demand Limit Opt

0/1

DSABLE/ENABLE

dem_sel

DSABLE

Motor Rated Kilowatts

50-9999

kW

motor_kw

145

Demand Watts Interval

5-60

MIN

dw_int

15

DESCRIPTION

STATUS

UNITS

POINT

DEFAULT

Control Point

ECW Control Option

0/1

DSABLE/ENABLE

ecw_opt

DSABLE

Temp Pulldown Deg/Min

2-10

^F

temp_ramp

3

Temperature Reset

RESET TYPE 1
Degrees Reset At 20 mA

–30- 30

^F

deg_20ma

10

RESET TYPE 2
Remote Temp —> No Reset

–40-245

DEG F

res_rt1

85

Remote Temp —> Full Reset

–40-245

DEG F

res_rt2

65

Degrees Reset

–30-30

^F

deg_rt

10

RESET TYPE 3
CHW Delta T —> No Reset

0-15

^F

restd_1

10

CHW Delta T —> Full Reset

0-15

^F

restd_2

0

Degrees Reset

–30-30

^F

deg_chw

5

Select/Enable Reset Type

0-3

res_sel

0

MENU

SERVICE

EQUIPMENT SERVICE

SELECT

RAMP_DEM

SELECT

MENU

SERVICE

EQUIPMENT SERVICE

SELECT

TEMP_CTL

SELECT