Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

J. CHILLER ALERTS (cont)

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,

alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

149

SENSOR ALERT

HIGH DISCHARGE
TEMP

149->Comp Discharge Temp
[VALUE] exceeded limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for proper inlet guide vane and diffuser
actuator operation (Size 5 compressor Only).
Check for fouled tubes or noncondensables in
the refrigerant system.

150

SENSOR ALERT

HIGH BEARING
TEMPERATURE

150->Comp Thrust Bearing
Temp [VALUE] exceeded limit
of [LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil filter.
Check oil level.

151

CONDENSER
PRESSURE ALERT

PUMP RELAY
ENERGIZED

151->High Condenser
Pressure [VALUE]: Pump
Energized to Reduce
Pressure.

Check sensor wiring and accuracy.
Check condenser flow and fluid
temperature.
Check for fouled tubes. This alarm is not
caused by the High Pressure Switch.

152

RECYCLE
ALERT

EXCESSIVE RECYCLE
STARTS

152->Excessive recycle starts. Chiller load is too low to keep compressor on

line and there has been more than
5 starts in 4 hours. Increase chiller load,
adjust hot gas bypass, increase RECYCLE
RESTART DELTA T from SETUP1 Screen.

153

no message:
ALERT only

no message;
ALERT only

153->Lead/Lag Disabled:
Duplicate Chiller Address;
Check Configuration

Illegal chiller address configuration in Lead/
Lag screen. Both chillers require a different
address.

154

POTENTIAL
FREEZE-UP

COND PRESS/TEMP
TOO LOW

154->Condenser freeze up
prevention

The condenser pressure transducer is read-
ing a pressure that could freeze the con-
denser tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN mode if the
vessel is evacuated.

155

OPTION SENSOR
FAULT

REMOTE RESET
SENSOR

155->Sensor Fault/Option
Disabled:
Remote Reset Sensor

Check sensor resistance or voltage drop.
Check for proper wiring.

156

OPTION SENSOR
FAULT

AUTO CHILLED
WATER RESET

156->Sensor Fault/Option
Disabled:
Auto Chilled Water Reset

Check sensor resistance or voltage drop.
Check for proper wiring.

157

OPTION SENSOR
FAULT

AUTO DEMAND
LIMIT INPUT

157->Sensor Fault/Option
Disabled:
Auto Demand Limit Input

Check sensor resistance or voltage drop.
Check for proper wiring.

158

SENSOR ALERT

SPARE TEMPERATURE
#1

158->Spare Temperature #1
[VALUE] exceeded limit of
[LIMIT].*

Check sensor resistance or voltage drop.
Check for proper wiring.

159

SENSOR ALERT

SPARE TEMPERATURE
#2

159->Spare Temperature #2
[VALUE] exceeded limit of
[LIMIT].*

Check sensor resistance or voltage drop.
Check for proper wiring.

160

DIFFUSER
ALERT

DIFFUSER
POSITION

160->Diffuser Position Alert;
Check Diffuser Configuration.

Check diffuser configuration in SETUP2
screen.