19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET

19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Pulldown Ramp Type:
Select: Temp=0, Load=1

0/1

1

Demand Limit + kW Ramp

Demand Limit Source
Select: Amps=0, kW=1

0/1

0

Motor Load Ramp% Min

5 to 20

10

Demand Limit Prop Band

3 to 15

%

10

Demand Limit At 20 mA

40 to 100

%

40

20 mA Demand Limit Opt

0/1

DSABLE/ENABLE

DSABLE

Motor Rated Kilowatts

50 to 9999

kW

145

Demand Watts Interval

5 to 60

MIN

15

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Control Point

ECW Control Option

0/1

DSABLE/ENABLE

DSABLE

Temp Pulldown Deg/Min

2 to 10

ˆF

3

Temperature Reset

RESET TYPE 1
Degrees Reset At 20 mA

–30 to 30

ˆF

10

RESET TYPE 2
Remote Temp -> No Reset

–40 to 245

DEG F

85

Remote Temp -> Full Reset

–40 to 245

DEG F

65

Degrees Reset

–30 to 30

ˆF

10

RESET TYPE 3
CHW Delta T -> No Reset

0 to 15

ˆF

10

CHW Delta T -> Full Reset

0 to 15

ˆF

0

Degrees Reset

–30 to 30

ˆF

5

Select/Enable Reset Type

0 to 3

0