Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 65

Advertising
background image

65

Dry Run to Test Start-Up Sequence

For electro-mechanical starters.

1. Disengage the main motor disconnect (CB1) on the start-

er front panel. This should only disconnect the motor
power. Power to the controls, oil pump, and starter con-
trol circuit should still be energized.

2. Observe the default screen on the CVC/ICVC: the status

message in the upper left-hand corner reads, “Manually
Stopped,” Press the

or

softkey to start.

If the chiller controls do not go into a start mode (“Unoc-
cupied Mode” is displayed) go to the SCHEDULE screen
and override the schedule or change the occupied
time. Press the

softkey to begin the start-up

sequences.

3. View the STARTUP display screen and verify the chilled

water and condenser water pumps have energized.

4. Verify the oil pump has started and is pressurizing the

lubrication system. After the oil pump has run about
11 seconds, the starter energizes (COMPRESSOR START
CONTACT
is closed) and goes through its start-up
sequence.

5. Check the main contactor (1M) for proper operation.
6. The PIC II eventually shows an alarm for motors amps

not sensed. Reset this alarm and continue with the initial
start-up.

For Benshaw Inc. solid-state starters:

1. Close the main motor disconnect (CB1). Voltage will be

applied to the compressor motor but the SCRs will not
fire (compressor motor will not rotate). Enter MENU 4 in
the Benshaw RediStart MICRO™ Menu structure at the
Benshaw display (see Input Service Configurations,
Change The Benshaw RediStart MICRO Software Con-
figuration page 57). Select Dry Run Mode and scroll to
YES.

2. Follow steps 2 through 4 for the electro-mechanical start-

ers. When the Ramp Time is set for less than 10 seconds
COMPRESSOR RUN CONTACT will close.

3. The PIC II eventually shows an alarm for motors amps

not sensed. Reset this alarm and enter MENU 4 in the
Benshaw display. Select Dry Run Mode and scroll to NO.
Continue with the initial start-up.

Check Motor Rotation

1. Engage the oil pump circuit breaker (CB3) located inside

the right hand side of the starter panel.

2. Then engage the control power circuit breaker (CB2) lo-

cated in the same section of the starter cabinet.

3. Finally close the main motor disconnect (CB1) on the

front of the starter panel.

4. The ISM mounted in the electro-mechanical starters

checks for proper phase rotation as soon as power is
applied to the starter and the PIC II controls power up.
Solid-state starters have phase protection and do not per-
mit a start if the phase rotation is not correct.

5. An alarm message will appear on the CVC/ICVC if the

phase rotation is incorrect. If this occurs reverse any 2 of
the 3 incoming power leads to the starter and reapply
power. The motor is now ready for a rotation check.

6. After the default screen status message states ‘Ready to

Start’ press the

softkey. The PIC II control per-

forms start-up checks.

7. When the starter is energized and the motor begins to

turn, check for clockwise motor rotation (Fig. 33).

Check Oil Pressure and Compressor Stop

1. When the motor is at full speed, note the differential oil

pressure reading on the CVC/ICVC default screen. It
should be between 18 and 30 psid (124 to 206 kPad).

2. Press the Stop button and listen for any unusual sounds

from the compressor as it coasts to a stop.

To Prevent Accidental Start-Up —

A chiller STOP

override setting may be entered to prevent accidental start-up
during service or whenever necessary. Access the MAINSTAT
screen and using the

or

softkeys, high-

light the CHILLER START/STOP parameter. Override the cur-
rent START value by pressing the

softkey. Press the

softkey followed by the

softkey. The word

SUPVSR! displays on the CVC/ICVC indicating the override
is in place.

To restart the chiller the STOP override setting must be re-

moved. Access the MAINSTAT screen and using

or

softkeys highlight CHILLER START/STOP. The

3 softkeys that appear represent 3 choices:

— forces the chiller ON

— forces the chiller OFF

— puts the chiller under remote or schedule

control.
To return the chiller to normal control, press the

softkey followed by the

softkey. For

more information, see Local Start-Up, page 46.

The default CVC/ICVC screen message line indicates

which command is in effect.

Check Chiller Operating Condition —

Check to

be sure that chiller temperatures, pressures, water flows, and
oil and refrigerant levels indicate the system is functioning
properly.

Instruct the Customer Operator —

Ensure the op-

erator(s) understand all operating and maintenance procedures.
Point out the various chiller parts and explain their function as
part of the complete system.
COOLER-CONDENSER — Float chamber, relief valves, re-
frigerant charging valve, temperature sensor locations, pressure
transducer locations, Schrader fittings, waterboxes and tubes,
and vents and drains.

CCN

LOCAL

LOCAL

LOCAL

Do not check motor rotation during coastdown. Rotation
may have reversed during equalization of vessel pressures.

NEXT

PREVIOUS

SELECT

STOP

ENTER

NEXT

PREVIOUS

START
STOP
RELEASE

RELEASE

ENTER

Fig. 33 — Correct Motor Rotation

Advertising