Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 83

Advertising
background image

83

Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

I. CHILLER PROTECT LIMIT FAULTS (cont)

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,

alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

J. CHILLER ALERTS

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

246

PROTECTIVE
LIMIT

INVALID DIFFUSER
CONFIG

246->Diffuser Control Invalid
Configuration:
Check SETUP2 Entries.

Check diffuser/guide vane schedule.

247

PROTECTIVE
LIMIT

DIFFUSER POSITION
FAULT

247->Diffuser Position Fault:
Check Guide Vane and Diffuser
Actuators

Check rotating stall transducer wiring and
accuracy.
Check diffuser schedule.
Check for proper operation of diffuser actuator
and inlet guide vane actuator.
Check diffuser coupling.
Check inlet guide vane operation.
Check inlet guide vane calibration.
Check diffuser/inlet guide vane schedule.
Check diffuser mechanical set-up for proper
orientation.
If not using variable diffuser, check that the
option has not been enabled.

248

PROTECTIVE
LIMIT

SPARE TEMPERATURE
#1

248->Spare Temperature #1
[VALUE] exceeded limit of
[LIMIT]*.

249

PROTECTIVE
LIMIT

SPARE TEMPERATURE
#2

249->Spare Temperature #2
[VALUE] exceeded limit of
[LIMIT]*.

250

PROTECTIVE
LIMIT

REFRIGERANT LEAK
SENSOR

250->Refrigerant Leak Sensor
[VALUE] exceeded Limit of
[LIMIT]*.

The refrigerant leak detector’s output wired to
J5-5 and J5-6 on the CCM module has
reached the alarm limit.
Check leak detector and for leaks.

251

PROTECTIVE
LIMIT

ISM CONFIG
CONFLICT

251->ISM Config Conflict (ISM
Uploaded); Verify to Reset Alarm

Confirm valid settings in ISM_CONF screen.

252

PROTECTIVE
LIMIT

ISM CONFIG
CONFLICT

252->ISM Config Conflict (ISM
Downloaded); Verify to Reset
Alarm

Confirm valid settings in ISM_CONF screen.

253

PROTECTIVE
LIMIT

GUIDE VANE
CALIBRATION

253->Guide Vane Fault [VALUE].
Check Calibration.

Enter Control Test and execute Guide Vane
Calibration. Check guide vane feedback (ter-
minals J4-9 and J4-10) on the CCM module.

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

140

SENSOR ALERT

LEAVING COND
WATER TEMP

140->Sensor Fault:
Check Leaving Cond Water
Sensor

Check sensor resistance or voltage drop.
Check for proper wiring.

141

SENSOR ALERT

ENTERING COND
WATER TEMP

141->Sensor Fault:
Check Entering Cond Water
Sensor

Check sensor resistance or voltage drop.
Check for proper wiring.

142

LOW OIL PRESSURE
ALERT

CHECK OIL FILTER

142->Low Oil Pressure Alert.
Check Oil Filter.

Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.

143

AUTORESTART
PENDING

LINE PHASE
LOSS

143->Line Phase Loss

Power loss has been detected in any phase.
Chiller automatically restarting.

144

AUTORESTART
PENDING

LINE VOLTAGE
DROP OUT

144->Single Cycle Line
Voltage Dropout

A drop in line voltage has been detected within
2 voltage cycles. Chiller automatically restarting if
Autorestart option is enabled.

145

AUTORESTART
PENDING

HIGH LINE
VOLTAGE

145>Line Overvoltage —
Average Line Volt [VALUE]

Check line power.

146

AUTORESTART
PENDING

LOW LINE
VOLTAGE

146->Line Undervoltage —
Average Line Volt [VALUE]

Check line power.

147

AUTORESTART
PENDING

STARTER MODULE
RESET

147->Starter Module Power-
On Reset When Running

ISM has detected a hardware fault and has reset.
Chiller automatically restarting.

148

AUTORESTART
PENDING

POWER LOSS

148->Control Power-Loss
When Running

Check control power.