CHANGE THE BENSHAW INC., RediStart MICRO™
SOFTWARE CONFIGURATION IF NECESSARY — Ben-
shaw starter configurations are checked and modified from the
menus in the Benshaw Redistart MICRO Default Display. See
Fig. 32 and Table 6 for default display and menu items. To ac-
cess the menus to perform checks and modifications, the Ben-
shaw starter must be powered up and its self-test must have
been successfully completed. The self-test takes place automat-
ically after power-up. Current transformer ratio configurations
and hardware switch settings checks are performed in the
MENU1 display screen. See Table 7 for menu structure and
Table 8 for switch settings.

1. Press the

softkey until the desired menu is se-

lected on the display.

2. Press the

softkey to access the displayed menu

items (Table 6).

3. Use the

or

arrow keys to scroll between menu

items until the desired item is reached on the display.

4. Press the

softkey to access the value to be

changed.

5. Use the

or

arrow keys to adjust the new displayed

value. The

key increases the value while the

key

decreases the value. Holding the arrow key will progres-
sively increase the rate of change. The value will stop
changing when either the factory set minimum or maxi-
mum value is reached. To make fine adjustments press
and release the arrow key.

6. When the correct value has been selected, press the

key to store the new configuration. At this

point, there are two options. The

key will return

the display to the main display. The

or

arrow keys

will move the display to the next menu item. When fin-
ished press the

key to return to the main display.

To view other settings and troubleshooting guide consult the

Benshaw RediStart MICRO instructional manual included in
the starter.

Table 6 — Benshaw RediStart

MICRO Menu Structure

Table 7 — Benshaw RediStart MICRO Menu Items*

*These values are not displayed in the ISM_CONFIG table.

Table 8 — Benshaw RediStart MICRO Current Transformer DIP Switch Settings

LEGEND

CT — Current Transformer

MENU

ENTER

ENTER

ENTER

MENU

MENU

MENU 1
Starter Setup

MENU 2
Meter Setup

MENU 3
Event
Recorder

MENU 4
Dry Run
Mode

Initial Current
as % RLA

Meter #1
display

Events 1-99

Dry Run
Mode

Max. Cur
As% LRA

Meter #2
display

Ramp Time
(sec.)

CT Ratio: 1

DESCRIPTION

RANGE

UNITS

DEFAULT

INITIAL CURRENT

50-300

%

125

MAX. CURR AS % LRA

30-70

%

55

RAMP TIME

5-30

SEC

15

CT RATIO

2640-5760

Enter Value from Table 8.

CURRENT TRANSFORMER CT1-CT3

Starter

Frame Size

(Amps)

Motor

RLA Range

(Amps)

CT

Ratio

MIcro Power Card (BIPCMIPWR-C4)

Overload Switch Settings

SW1-1

SW1-2

200 Amps

95- 135 Amps

3900:1

OFF

OFF

136- 200 Amps

5760:1

OFF

OFF

300 Amps

201- 231 Amps

2640:1

ON

OFF

232- 300 Amps

3900:1

ON

OFF

480 Amps

301- 340 Amps

3900:1

ON

OFF

341- 480 Amps

5760:1

ON

OFF

600 Amps

481- 580 Amps

2640:1

ON

ON

581- 600 Amps

3900:1

ON

ON

740 Amps

601- 740 Amps

3900:1

ON

ON

1250 Amps

741- 855 Amps

3900:1

ON

ON

856-1250 Amps

5760:1

ON

ON

FAULT

RESET

MENU

ENTER

DISPLAY

SCROLL UP

SCROLL DOWN

MENU
SELECTION

MENU ENTRY
DATA ENTRY

STOP I = OA

READY V = 461V

RediStart MICRO

Fig. 32 — Benshaw RediStart

MICRO Default Display