Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

I. CHILLER PROTECT LIMIT FAULTS (cont)

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

227

PROTECTIVE
LIMIT

OIL PRESS
SENSOR FAULT

227->Oil Pump Delta P
[VALUE] exceeded limit of
[LIMIT]*.

Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check transducer calibration.

228

PROTECTIVE
LIMIT

LOW OIL
PRESSURE

228->Oil Pump Delta P
[VALUE] exceeded limit of
[LIMIT].*

Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check oil level.
Check for partially closed service valves.
Check oil filters.
Check for foaming oil at start-up.
Check transducer calibration.

229

PROTECTIVE
LIMIT

LOW CHILLED
WATER FLOW

229->Low Chilled Water
Flow; Check Delta P Config
& Calibration

Perform pump control test.
Check transducer accuracy and wiring.
Check water valves.
Check transducer calibration.

230

PROTECTIVE
LIMIT

LOW CONDENSER
WATER FLOW

230->Low Condenser Water
Flow; Check Delta P Config
& Calibration

Perform pump control test.
Check transducer accuracy and wiring.
Check water valves.
Check transducer calibration.

231

PROTECTIVE
LIMIT

HIGH DISCHARGE
TEMP

231->Comp Discharge
Temp [VALUE] exceeded
limit of [LIMIT].*

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper condenser flow and temperature.
Check for proper inlet guide vane and diffuser
actuator operation.
Check for fouled tubes or noncondensables in the
system.

232

PROTECTIVE
LIMIT

LOW REFRIGERANT
TEMP

232->Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.

Check for proper refrigerant charge.
Check float operation.
Check for proper fluid flow and temperature.
Check for proper inlet guide vane operation.

233

PROTECTIVE
LIMIT

HIGH MOTOR
TEMPERATURE

233->Comp Motor Winding
Temp [VALUE] exceeded
limit of [LIMIT]*.

Check motor sensors wiring and accuracy.
Check motor cooling line for proper operation, or
restrictions.
Check for excessive starts within a short time span.

234

PROTECTIVE
LIMIT

HIGH BEARING
TEMPERATURE

234->Comp Thrust Bearing
Temp [VALUE] exceeded
limit of [LIMIT]*.

Check oil heater for proper operation.
Check for low oil level, partially closed oil supply
valves, clogged oil filters, etc.
Check the sensor wiring and accuracy.

235

PROTECTIVE
LIMIT

HIGH CONDENSER
PRESSURE

235->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.

Check for high condenser water temperatures, low
water flow, fouled tubes.
Check for division plate/gasket bypass.
Check for noncondensables.
Check transducer wiring and accuracy.

236

PROTECTIVE
LIMIT

CCN OVERRIDE
STOP

236->CCN Override Stop
while in LOCAL run mode

CCN has signaled the chiller to stop. Reset and
restart when ready. If the signal was sent by the
CVC/ICVC, release the stop signal on the STATUS01
table.

237

PROTECTIVE
LIMIT

SPARE SAFETY
DEVICE

237->Spare Safety Device

Spare safety input has tripped or factory installed
jumper is not present.

238

PROTECTIVE
LIMIT

EXCESSIVE
COMPR SURGE

238->Compressor Surge:
Check condenser water
temp and flow

Check condenser flow and temperatures.
Check surge protection configuration.

239

PROTECTIVE
LIMIT

TRANSDUCER
VOLTAGE FAULT

239->Transducer Voltage
Ref [VALUE] exceeded limit
of [LIMIT]*.

240

PROTECTIVE
LIMIT

LOW DISCHARGE
SUPERHEAT

240->Check for Oil in
Refrigerant or Overcharge
of Refrigerant

241

LOSS OF
COMMUNICATION

WITH STARTER
MODULE

241->Loss of Communica-
tion With Starter.

Check wiring to ISM.

242

LOSS OF
COMMUNICATION

WITH CCM
MODULE

242->Loss of Communica-
tion With CCM.

Check wiring to CCM.

243

POTENTIAL
FREEZE-UP

EVAP PRESS/TEMP
TOO LOW

243->Evaporator Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.

Check for proper refrigerant charge.
Check float operation.
Check for proper fluid flow and temperature.
Check for proper inlet guide vane operation.

244

POTENTIAL
FREEZE-UP

COND PRESS/TEMP
TOO LOW

244->Condenser Refrig
Temp [VALUE] exceeded
limit of [LIMIT]*.

245

PROTECTIVE
LIMIT

VFD SPEED
OUT OF RANGE

245->Actual VFD Speed
[VALUE] exceeded limit of
[LIMIT]*.