Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 95

Advertising
background image

95

Table 17A — 19XR Waterbox Cover Weights — English (lb)

LEGEND

NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Table 6.

RIG MACHINE COMPONENTS —

Refer to instructions

below, Fig. 6-9, and Carrier Certified Prints for machine com-
ponent disassembly.

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 1

FRAME 2

FRAME 3

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/

CONDENSER

NIH, 1 Pass Cover, 150 psig

177

204

320

350

320

350

NIH, 2 Pass Cover, 150 psig

185

218

320

350

320

350

NIH, 3 Pass Cover, 150 psig

180

196

300

340

300

340

NIH/MWB End Cover, 150 psig

136

136

300

300

300

300

NIH, 1 Pass Cover, 300 psig

248

301

411

486

411

486

NIH, 2 Pass Cover, 300 psig

255

324

411

518

411

518

NIH, 3 Pass Cover, 300 psig

253

288

433

468

433

468

NIH/MWB End Cover, 300 psig

175

175

400

400

400

400

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 4

FRAME 5

FRAME 6

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/

CONDENSER

NIH, 1 Pass Cover, 150 psig

148

185

168

229

187

223

NIH, 2 Pass Cover, 150 psig

202

256

224

298

257

330

NIH, 3 Pass Cover, 150 psig

473

489

629

655

817

843

NIH/MWB End Cover, 150 psig

317

317

393

393

503

503

NIH, 1 Pass Cover, 300 psig

593

668

764

839

959

1035

NIH, 2 Pass Cover, 300 psig

594

700

761

878

923

1074

NIH, 3 Pass Cover, 300 psig

621

656

795

838

980

1031

NIH/MWB End Cover, 300 psig

569

569

713

713

913

913

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 7 COOLER

FRAME 7 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/

CONDENSER

NIH, 1 Pass Cover, 150 psig

329

441

329

441

NIH, 2 Pass Cover, 150 psig

426

541

426

541

NIH, 3 Pass Cover, 150 psig

1202

1239

1113

1171

NIH/MWB End Cover, 150 psig

789

789

703

703

NIH, 1 Pass Cover, 300 psig

1636

1801

1472

1633

NIH, 2 Pass Cover, 300 psig

1585

1825

1410

1644

NIH, 3 Pass Cover, 300 psig

1660

1741

1496

1613

NIH/MWB End Cover, 300 psig

1451

1451

1440

1440

HEAT

EXCHANGER

WATERBOX

DESCRIPTION

FRAME 8 COOLER

FRAME 8 CONDENSER

Standard

Nozzles

Flanged

Standard

Nozzles

Flanged

COOLER/

CONDENSER

NIH, 1 Pass Cover, 150 psig

417

494

417

494

NIH, 2 Pass Cover, 150 psig

531

685

531

685

NIH, 3 Pass Cover, 150 psig

1568

1626

1438

1497

NIH/MWB End Cover, 150 psig

1339

1339

898

898

NIH, 1 Pass Cover, 300 psig

2265

2429

1860

2015

NIH, 2 Pass Cover, 300 psig

2170

2499

1735

2044

NIH, 3 Pass Cover, 300 psig

2273

2436

1883

1995

NIH/MWB End Cover, 300 psig

1923

1923

1635

1635

NIH

Nozzle-in-Head

MWB —

Marine Waterbox

IMPORTANT: Only a qualified service technician should
perform this operation.

Do not attempt to disconnect flanges while the machine is
under pressure. Failure to relieve pressure can result in per-
sonal injury or damage to the unit.

Before rigging the compressor, disconnect all wires enter-
ing the power panel.

Advertising