Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual

Page 132

Advertising
background image

CL-8

19XR, XRV PIC II SETUP2 TABLE CONFIGURATION SHEET

DESCRIPTION

STATUS

UNITS

DEFAULT

VALUE

Capacity Control

Proportional Inc Band

2 to 10

6.5

Proportional DEC Band

2 to 10

6.0

Proportional ECW Gain

1 to 3

2.0

Guide Vane Travel Limit

30 to 100

%

80

Diffuser Control

Diffuser Option

0 to 1

DSABLE/ENABLE

DSABLE

Guide Vane 25% Load Pt

0 to 78

%

25

Diffuser 25% Load Point

0 to 100

%

0

Guide Vane 50% Load Pt

0 to 78

%

50

Diffuser 50% Load Point

0 to 100

%

0

Guide Vane 75% Load Pt

0 to 78

%

50

Diffuser 75% Load Point

0 to 100

%

0

Diffuser Full Span mA

15 to 22

mA

18

VFD Speed Control

VFD Option

0/1

DSABLE/ENABLE

DSABLE

VFD Gain

0.1 to 1.5

0.75

VFD Increase Step

1 to 5

%

2

VFD Minimum Speed

65 to 100

%

70

VFD Maximum Speed

90 to 100

%

100

VFD Current Limit

0 to 99999

Amp

250