Table 11 — CVC/ICVC Primary and Secondary Messages and

Custom Alarm/Alert Messages with Troubleshooting Guides (cont)

G. NORMAL RUN WITH OVERRIDES

*[LIMIT] is shown on the CVC/ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override,

alert, or alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault con-
dition.

H. OUT-OF-RANGE SENSOR ALARMS

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

120

RUN CAPACITY
LIMITED

HIGH CONDENSER
PRESSURE

120->Condenser Pressure
[VALUE] exceeded limit of [LIMIT]*.

Check for high condenser water temperatures.
Check setting in SETUP1.

121

RUN CAPACITY
LIMITED

HIGH MOTOR
TEMPERATURE

121->Comp Motor Winding Temp
[VALUE] exceeded limit of [LIMIT]*.

Check motor cooling lines.
Check for closed valves.
Check setting in SETUP1.

122

RUN CAPACITY
LIMITED

LOW EVAP
REFRIG TEMP

122->Evaporator Refrig Temp
[VALUE] exceeded limit of [LIMIT]*.

Check refrigerant charge.
Check for low entering cooler temperatures.

123

RUN CAPACITY
LIMITED

HIGH COMPRESSOR
LIFT

123->Surge Prevention Override:
Lift Too High For Compressor.

Check for high condenser water temperatures or
low suction temperature.

124

RUN CAPACITY
LIMITED

MANUAL GUIDE
VANE TARGET

124->Run Capacity Limited:
Manual Guide Vane Target.

Target guide vane point has been forced in
MAINSTAT screen. Release force to continue
normal operation.

125

RUN CAPACITY
LIMITED

LOW DISCHARGE
SUPERHEAT

No messages.

Check oil charge.
Check refrigerant charge.

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

ALARM MESSAGE

PRIMARY CAUSE

ADDITIONAL

CAUSE/REMEDY

260

SENSOR
FAULT

LEAVING CHILLED
WATER

260->Sensor Fault:
Leaving Chilled Water

Check sensor resistance or voltage drop.
Check for proper wiring.

261

SENSOR
FAULT

ENTERING CHILLED
WATER

261->Sensor Fault:
Entering Chilled Water

Check sensor resistance or voltage drop.
Check for proper wiring.

262

SENSOR
FAULT

CONDENSER
PRESSURE

262->Sensor Fault:
Condenser Pressure

Check sensor wiring.

263

SENSOR
FAULT

EVAPORATOR
PRESSURE

263->Sensor Fault:
Evaporator Pressure

Check sensor wiring.

264

SENSOR
FAULT

COMPRESSOR
BEARING TEMP

264->Sensor Fault:
Comp Thrust Bearing Temp

Check sensor resistance or voltage drop.
Check for proper wiring.

265

SENSOR
FAULT

COMPRESSOR
MOTOR TEMP

265->Sensor Fault:
Comp Motor Winding Temp

Check sensor resistance or voltage drop.
Check for proper wiring.

266

SENSOR
FAULT

COMP DISCHARGE
TEMP

266->Sensor Fault:
Comp Discharge Temp

Check sensor resistance or voltage drop.
Check for proper wiring.

267

SENSOR
FAULT

OIL SUMP TEMP

267->Sensor Fault:
Oil Sump Temp

Check sensor resistance or voltage drop.
Check for proper wiring.

268

SENSOR
FAULT

COMP OIL
PRESS DIFF

268->Sensor Fault:
Oil Pump Delta P

Check sensor wiring and accuracy.

269

SENSOR
FAULT

CHILLED WATER
FLOW

269->Sensor Fault:
Chilled Water Delta P

Check sensor wiring and accuracy.

270

SENSOR
FAULT

COND WATER
FLOW

270->Sensor Fault:
Cond Water Delta P

Check sensor wiring and accuracy.

271

SENSOR
FAULT

VFD SPEED SENSOR
OUT OF RANGE

271->Sensor Fault:
Check Actual VFD Speed Sensor

Check voltage input on terminals J6-1 and J6-2 on
the ISM module. Check wiring.

273

SENSOR
FAULT

VFD SPEED OUT OF
RANGE

273->Sensor Fault:
Check Actual VFD Speed Sensor

Check VFD feedback 0-5 vac. Calibrate VFD
speed reference signal.