19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Auto Restart Option

0/1

DSABLE/ENABLE

DSABLE

Remote Contacts Option

0/1

DSABLE/ENABLE

DSABLE

Soft Stop Amps Threshold

40 to 100

%

100

Surge/Hot Gas Bypass

Surge Limit/HGBP Option
Select: Surge=0, HGBP=1

0/1

0

Min. Load Point (T1, P1)
Surge/HGBP Delta T1

0.5 to 20

ˆF

1.5

Surge/HGBP Delta P1

30 to 170

PSI

50

Full Load Point (T2, P2)
Surge/HGBP Delta T2

0.5 to 20

ˆF

10

Surge/HGBP Delta P2

50 to 170

PSI

85

Surge/HGBP Deadband

0.5 to 3

ˆF

1

Surge Protection

Surge Delta% Amps

5 to 20

%

10

Surge Time Period

7 to 10

MIN

8

Ice Build Control

Ice Build Option

0/1

DSABLE/ENABLE

DSABLE

Ice Build Termination
0=Temp, 1=Contacts, 2=Both

0 to 2

0

Ice Build Recycle

0/1

DSABLE/ENABLE

DSABLE

Refrigerant Leak Option

0/1

DSABLE/ENABLE

DSABLE

Refrigerant Leak Alarm mA

4 to 20

mA

20

Head Pressure Reference

Delta P at 0% (4 mA)

20 to 60

psi

25

Delta P at 100% (20 mA)

20 to 60

psi

35

Minimum Output

0 to 100

%

0