9. Setting the shift target value

Set this value to shift the current value by another amount.

Press the [Up] and [Down] arrow buttons simultaneously to shift the current
value to the set value with the shift target value.
The shift status is retained even if the power is turned off.

Press the [Up] and [Down] arrow buttons simultaneously and

hold them to clear the shifted target value.

The amplifier does not retain the amount of shift when shifting with external
input. (It is cleared when the power is turned off.) To retain the amount of
shift, press the [Up] and [Down] arrow buttons simultaneously and perform
shift.

When performing reference surface calibration while edge hold mode (A-1
mode) is set, the value is always shifted to 0.

Shift is only a effective on the selected bank.

„

10. Distance display setting

Sets whether to use the side close to the sensor head as the positive direction

(normal) or negative direction (reverse).

„

11. Eco display setting

Set this parameter to reduce the consumption current or to stop displaying

specific values. When running in power saving (eco) mode, pressing any button

returns the sensor to normal operations.

The main screen switches to eco mode if no operations take place for 30

seconds.

Output circuit

GV-21/22 (NPN output)

* GV-21 only

GV-21P/22P (PNP output)

* GV-21P only

Power is supplied to the expansion unit GV-22(P) from the expansion connector on

the back of the main unit GV-21(P). The power wires (brown and blue) of the main

unit and those of the expansion unit are common inside through the connector.

Input circuit

GV-21/22 (NPN output)

* GV-21 only

GV-21P/22P (PNP output)

* GV-21P only

Purple line. . . . . . . Laser emission stop input

Pink line . . . . . . . . External input function

*

* The external input function can be set to one of the following.

Not used

Shift

input

Bank switching input

Timing

input

Item

Setting range

Default value

Shift target
value

-199 to 999

0

Setting item

Description

Default value

nor (Normal)

The display value increases as the target
comes closer to the sensor head.

{

rEv (Reverse)

The display value decreases as the target
comes closer to the sensor head.

Setting item

Description

Default value

oFF

Turns off the eco display.

{

bAr

Turns off the digital display.

on

The digital display (green) flashes in
sequence. Bar display and channel No.
indicators are turned off.

Error Displays and Corrective Actions

Error indication

Error contents

Remedy

Head error

Sensor head is not
connected.
Head cable is broken.
Sensor head is
damaged

Check that the sensor head is

connected.

Check that the head cable is not

broken.

Check the connection of the

head cable to the connector.

After checking these points, turn

on the power again.

Overcurrent error

Overcurrent is flowing
through the output wire

Check the load and reduce the

current to be within the rated

range.

Check that the output wire does not

touch another wire or a frame.

EEPROM error

Data read/write error

Perform initialization.

Data has been written in
the EEPROM over 1
million times and can no
longer be updated.

If you need to write more data,
replace the amplifier unit.

There is no workpiece
or background within
the detection distance
range, or no light is
entering the receiver.

Set a workpiece or background in
the distance for detection from the
sensor.

Reading exceeds the
detection distance
range.

Set a workpiece or background in
the distance for detection from the
sensor.

Light intensity is
saturated.

Tilt the sensor head so that specular
reflection does not enter the sensor.

Reference

1
2

1
2

1
2

1
2

1
2

1
2

Troubleshooting

Problem

Cause and solutions

The current value is
larger than the setting
value, but the output is
not reversed.

This type of problem sometimes occurs when multiple
reflection occurs while using the distance detecting
method. If this problem occurs, use the reference
surface detection (DATUM) method and configure the
sensitivity setting.
If multiple reflection occurs, the spot reflection (1spot)
indicator turns off.

"Distance detection method (Normal)" (page 4)

"Reference surface detection (DATUM) method

(Application)" (page 5)

"Sensor amplifier part names" (page 3)

The external input does
not function.

Check the settings for the external input.

"8. External input function setting" (page 8)

The current settings can
no longer be
determined. The user
wants to return the unit
to the factory defaults.

Perform initial reset (initialization).

"Initial reset (initialization) and custom save function"

(page 6)

I/O Circuit Diagram

5-40 V DC

10-30 V DC

Load

Black/white (control output 1/2)

Brown *

Blue *

Sensor main circuit

Ov

ercurrent protection circuit

0 V

10-30 V DC

Load

Black/white (control output 1/2)

Brown *

Blue *

Sensor main circuit

Ov

ercurrent protection circuit

(Short-circuit current 1 mA max.)

PLC etc.

Purple/pink (input)

Sensor main circuit

Blue *

5 V DC

0 V

PLC etc.

Purple/pink (input)

Sensor main circuit

Brown *

10-30 V DC