2 i/o communication, Co mm u ni c a ting w ith t he fd -m h s er ie s – KEYENCE DL-DN1 User Manual

Page 41

Advertising
background image

3-2 I/O Communication

3-13

3

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-M

H

s

er

ie

s

- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (FD-MH) -

IN area

n: The first device number assigned to the DL-DN1
The device assignments are the same for all 3-output modes including extended
modes.

5-output mode

OUT area

m: The first device number assigned to the DL-DN1

Device

(DEC)

Name

Bit 7

Bit 6

···

Bit 1

Bit 0

Bit 15

Bit 14

···

Bit 9

Bit 8

n+7

Setting-value rewrite error

ID08

ID07

···

ID02

ID01

Reserved

ID15

···

ID10

ID09

n+8

Instantaneous fl ow rate
setting 1 (P1) rewrite
complete

ID08

ID07

···

ID02

ID01

Reserved

ID15

···

ID10

ID09

n+9

Instantaneous fl ow rate
setting 2 (P2) rewrite
complete

ID08

ID07

···

ID02

ID01

Reserved

ID15

···

ID10

ID09

n+10

Temperature upper limit
setting rewrite complete

ID08

ID07

···

ID02

ID01

Reserved

ID15

···

ID10

ID09

Device

(DEC)

Name

Bit 7

Bit 6

...

Bit 1

Bit 0

Bit 15

Bit 14

...

Bit 9

Bit 8

m+5

Request to rewrite
instantaneous flow rate
setting 1 (P1)

ID08

ID07

...

ID02

ID01

Reserved

ID15

...

ID10

ID09

m+6 to 7

Instantaneous flow rate
setting 1 (P1)

Instantaneous flow rate setting 1 (P1) to be rewritten

(4-byte signed integer)

m+8

Request to rewrite
instantaneous flow rate
setting 2 (P2)

ID08

ID07

...

ID02

ID01

Reserved

ID15

...

ID10

ID09

m+9 to 10

Instantaneous flow rate
setting 2 (P2)

Instantaneous flow rate setting 2 (P2) to be rewritten

(4-byte signed integer)

m+11

Request to rewrite
temperature upper limit
setting

ID08

ID07

...

ID02

ID01

Reserved

ID15

...

ID10

ID09

m+12 to 13

Temperature upper limit
setting

Temperature upper limit setting to be rewritten

(4-byte signed integer)

m+14

Request to rewrite
temperature lower limit
setting

ID08

ID07

...

ID02

ID01

Reserved

ID15

...

ID10

ID09

m+15 to 16

Temperature lower limit
setting

Temperature lower limit setting to be rewritten

(4-byte signed integer)

m+17

Request to rewrite
integrated flow quantity
setting 1

ID08

ID07

...

ID02

ID01

Reserved

ID15

...

ID10

ID09

m+18 to 19

Integrated flow quantity
setting 1

Integrated flow quantity setting 1 to be rewritten

(4-byte signed integer)

Advertising