Chapter 5. L-Cell Installation on Skirt-Supported Vessels

5-5

Figure 5-6. Perspective View — L-Cell and Junction Box Locations (Aluminum)

Mount Junction
Box 6’ (1.8m)
above Foundation

L-Cell B

Center L-Cells
Vertically
on Panel

Location

Centerline

L-Cell D

Alternate
Conduit
Locations

Notes:
• L-Cells A and C are on inside of skirt.
• L-Cells B and D are on outside of skirt.
• Distribute L-Cells symmetrically around vessel.
• Minimum panel height for L-Cell installation is 6’ (1.8m).
• Junction box is on inside of skirt, 6’ (1.8m) above foundation.
• Run conduit 1’ (0.3m) below junction box or near foundation,

so it does not interfere with L-Cell placement.

1’

(0.3m)

L-Cell C

L-Cell A

Figure 5-7. L-Cell Detail at Door

Approximately

3.9’ (1.2m)*

Approximately

3.9’ (1.2m)*

2.6’ (0.8m)
Minimum

Top of Tier

Center first
L-Cell set
vertically
between top
of door
frame and
top of tier

Approximately

3.9’ (1.2m)*

Approximately

3.9’ (1.2m)*

Centerline

Door

Less than
2.6’ (0.8m)

Top of Tier

Distance from Top of Door Frame to

Top of Tier Greater than 2.6’ (0.8m)

Distance from Top of Door Frame to

Top of Tier Less than 2.6’ (0.8m)

*Note: See Figure 5-5 for spacing, which is dependent on skirt diameter.

O

I

O

I

O

I

I

O

I

O

O

I

Centerline

Door

Legend:
O = outside L-Cell
I = inside L-Cell

Split first L-Cell set

— Locate 1

L-Cell on each side

of door and center

vertically in tier

Centerline
L-Cell to edge
of door frame
7.9” (20 cm)