Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 10

Advertising
background image

AERCO ProtoNode Gateway

User Manual

Page 10 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

NOTE

If there are two instances of the same MAC address, it could
result in a network crash. The node offset will allow you to avoid
this situation.

2.4.2.1 Set Node_Offset to Assign Specific Device instances for BACnet

MS/TP and BACnet/IP

• If the Device Instances need to be set for addresses other than 1 to 255, change

the Node-Offset (See Figure 2-2)

• The BACnet Device Instance can range from 1 to 4,194,303.
• BACnet/IP and BACnet MS/TP Addressing: The BACnet device instances will

be set by taking the Node_Offset found in Web Configurator (see Figure 2-2)
and adding it to the value of the A Bank DIP switches. When more than one
device is connected to the ProtoNode, the subsequent BACnet device instances
will be sequential.

• Set the PC address to be on the same subnet as the ProtoNode. See section

5.3 on how to change the IP address. (See Figure 2-2)

• Open the PC browser to default IP address, which will bring you to the FST Web

Configurator for the ProtoNode.

• Change the Node offset to meet the required device instance.

For example:

o

Node_Offset = 20000.

o

A Bank DIP Switch = 11

o

Device 1 Device Instance = 20011

NOTE

The A bank dip switch setting + node offset = device instance
setting.

FIGURE 2-2: MAC Address DIP Switches

Advertising