Table C-4: Four Modulex and One ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon Direction

ModBus/Unit

Address

1

02-Target Setpoint

effectsetpt_1

AV:135

data
float

63

nvoMlxSetpt1

inc count (9)

Output (non-polled)

41019/1

1

03-Req Outlet
Temp

setpt_1

AV:136

data
float

64

nviMlxSetptRq1

inc count (9)

Input (non-polling)

41005/1

1

04-Net Direct Drive

boilercmd_1

AV:137

data
float

65

nviMlxCmd1

inc count (9)

Input (non-polling)

40002/1

1

05-Mod Lev In

boilerload_1

AV:138

data
float

66

nvoMlxLoad1

inc count (9)

Output (non-polled)

41201/1

1

06-Flow Sens
Temp

localsuptemp_1

AV:139

data
float

67

nvoMlxSupTmp1

inc count (9)

Output (non-polled)

41003/1

1

07-Display Code

dispcode_1

AV:140

data
float

68

nvoMlxDispCode1

inc count (9)

Output (non-polled)

30001/1

1

11-Error Code

errcode_1

AV:1

data
float

69

nvoMlxErrCode1

51

Output (non-polled)

40001/1

1

08-Unit Status

unitstat_1

AV:141

data
float

150

nvoMlxStat1

inc count (9)

Output (non-polled)

30002/1

1

09-Ret Flow Temp

returntemp_1

AV:2

data
float

151

nvoMlxRetTmp1

inc count (9)

Output (non-polled)

41004/1

Mlx Addr 2

2

01-Act Mod Lev

boilerstate_2

AV:144

data
float

153

nvoMlxState2

inc count (9)

Output (non-polled)

41009/2

2

02-Target Setpoint

effectsetpt_2

AV:145

data
float

154

nvoMlxSetpt2

inc count (9)

Output (non-polled)

41019/2

2

03-Req Outlet
Temp

setpt_2

AV:146

data
float

155

nviMlxSetptRq2

inc count (9)

Input (non-polling)

41005/2

2

04-Net Direct Drive

boilercmd_2

AV:147

data
float

156

nviMlxCmd2

inc count (9)

Input (non-polling)

40002/2

2

05-Mod Lev In

boilerload_2

AV:148

data
float

157

nvoMlxLoad2

inc count (9)

Output (non-polled)

41201/2

2

06-Flow Sens
Temp

localsuptemp_2

AV:149

data
float

158

nvoMlxSupTmp2

inc count (9)

Output (non-polled)

41003/2

2

07-Display Code

dispcode_2

AV:150

data
float

159

nvoMlxDispCode2

inc count (9)

Output (non-polled)

30001/2

2

11-Error Code

errcode_2

AV:4

data
float

160

nvoMlxErrCode2

51

Output (non-polled)

40001/2