Chapter 4, Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 23

Advertising
background image

AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 23 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

CHAPTER 4:

4.1 Wiring ProtoNode RER to RS-485 Field Protocol (BACnet MS/TP

or Metasys N2)

Connect BAS BACnet MS/TP or Metasys N2 RS-485 port to the 3-pin RS-485 connector on
ProtoNode RER as shown below.

Figure 4-1: Connection from ProtoNode to RS-485 Field Protocol

– BACnet MS/TP

NOTE

See Section 5 for information on connecting ProtoNode RER to
BACnet/IP network.

If the ProtoNode is the last device on the BACnet MS/TP or Metasys N2 trunk or if
using an RS232 to RS485 converter, then the End-Of-Line Terminator may need to
be enabled (See Figure 4-2). It is disabled by default.

Figure 4-2: RS-485 EOL Switch

TABLE 4-1: RER 3-Pin Connector Wiring

Pin #

BAS RS-485

Function

Pin 1

RS-485 +

RS-485 +

Pin 2

RS-485 -

RS-485 -

Pin 3

-

RS-485 GND

End of Line
Termination
Switch
(Move switch left to
terminate)