AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 91 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

Appendix C.6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II

Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon

Direction

ModBus/

Unit

Address

Mlx Addr 1

1

01-Act Mod Lev

boilerstate_1

AV:121

data
float

121

nvoMlxState1

inc count (9)

Output (non-polled)

41009/1

1

02-Target Setpoint

effectsetpt_1

AV:122

data
float

122

nvoMlxSetpt1

inc count (9)

Output (non-polled)

41019/1

1

03-Req Outlet
Temp

setpt_1

AV:123

data
float

123

nviMlxSetptRq1

inc count (9)

Input (non-polling)

41005/1

1

04-Net Direct Drive

boilercmd_1

AV:124

data
float

124

nviMlxCmd1

inc count (9)

Input (non-polling)

40002/1

1

05-Mod Lev In

boilerload_1

AV:125

data
float

125

nvoMlxLoad1

inc count (9)

Output (non-polled)

41201/1

1

06-Flow Sens
Temp

localsuptemp_1

AV:126

data
float

126

nvoMlxSupTmp1

inc count (9)

Output (non-polled)

41003/1

1

07-Display Code

dispcode_1

AV:127

data
float

127

nvoMlxDispCode1

inc count (9)

Output (non-polled)

30001/1

1

11-Error Code

errcode_1

AV:128

data
float

128

nvoMlxErrCode1

51

Output (non-polled)

40001/1

1

08-Unit Status

unitstat_1

AV:129

data
float

129

nvoMlxStat1

inc count (9)

Output (non-polled)

30002/1

1

09-Ret Flow Temp

returntemp_1

AV:130

data
float

130

nvoMlxRetTmp1

inc count (9)

Output (non-polled)

41004/1

Mlx Addr 2

2

01-Act Mod Lev

boilerstate_2

AV:131

data
float

131

nvoMlxState2

inc count (9)

Output (non-polled)

41009/

2

02-Target Setpoint

effectsetpt_2

AV:132

data
float

132

nvoMlxSetpt2

inc count (9)

Output (non-polled)

41019/2

2

03-Req Outlet
Temp

setpt_2

AV:133

data
float

133

nviMlxSetptRq2

inc count (9)

Input (non-polling)

41005/2

2

04-Net Direct Drive

boilercmd_2

AV:134

data
float

134

nviMlxCmd2

inc count (9)

Input (non-polling)

40002/2

2

05-Mod Lev In

boilerload_2

AV:135

data
float

135

nvoMlxLoad2

inc count (9)

Output (non-polled)

41201/2