Table B-3: AERCO BMS II & BCM Point Definitions (Cont.)

Point Name

BAS Modbus

Data Address

GF-108, GF-
124, GF-114

Point Name

Reg.

Type

Modbus

Data

Address

(Hex/Dec.)

Units (Range)

Modulex Boiler with BCM - Cont.

06-Flow Sens Temp
(Flow Sensor
Temperature)

41003

Flow Sensor
Temperature

Holding

0x03EA /

1002

°F (14 to 212) (Value x 10)

07-Display Code

30001

Status & Error
Code
(C-more
compatible)

Input

0x0000 / 0

Enum (2,8,10,18,23,32,38,42)
2 = Standby
8 = High Temp Switch Open
10 = Low Gas Press Switch Open
18 = Air Flow Switch Open During
Ignition
23 = Flame Loss During Run
32 = Residual Flame
38 = Other Conditions Not Listed
42 = Outlet (Flow) Temp Sensor Fault

11-Error Code

40001

Error Code

Holding

0x0000 / 0

(0 to 0xFFFF)
LSB = Error Code
MSB = Id Code Of Fault Device (0 =
BMM#0, 7 = BMM#7, 255 = BCM).
See Appendix B.

08-Unit Status

30002

Unit Status
(C-more
Compatible)

Input

0x0001 / 1

Enum (1,3,5)
1 = Standby (ready to run but not fired)
3 = Fired
5 = Fault

09-Ret Flow Temp
(Return Flow
Temperature)

41004

Return Flow
Temperature

Holding

0x03EB /

1003

°F (32 to 212) (Value x 10)

IMPORTANT

Some Modbus addresses specified in this manual are written generically in
hexadecimal/decimal format. However, many Building Automation Systems
utilize another form of addressing where:

• 40001 is added to the generic address for a Holding Register

address.

• 30001 is added to the generic address for an Input Register

address.

Check the addressing scheme being used by the BAS interfaced to the
ProtoNode.