Aerco protonode gateway – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual
Page 34

AERCO ProtoNode Gateway
User Manual
Page 34 of 126
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0080_0H
11/06/2014
Ph.: 800-526-0288
GF-129
6.3 Set IP Address for BACnet/IP and Modbus TCP via RUInet
1) From the main menu, press “I” to enter the Edit IP Address Settings menu.
2) Press “1” to modify the IP address of the Ethernet adapter.
3) Type in a new IP address in the format 192.168.2.X and press <Enter>.
4) If necessary, press “2” to and change the netmask.
5) Type in a new Subnet Mask and press <Enter>.
6) If necessary, press “3” to and change the IP Gateway.
7) Type in a new IP Gateway and press <Enter>.
8) Note: If the ProtoNode is connected to a router, the IP Gateway of the ProtoNode
should be set to the IP address of the router that it is connected to.
9) Unplug Ethernet cable from PC and connect it to the network hub or router.