Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 100

Advertising
background image

AERCO ProtoNode Gateway

User Manual

Page 100 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon

Direction

ModBus/

Unit

Address

17

02-Setpoint

effectsetpt_17

AV:172

data
float

172

nvoEcsSetpt17

inc count (9)

Output (non-polled)

30006/17

17

03-RmSetpt

rmsetpt_17

AV:173

data
float

173

nviEcsSetptRq17

inc count (9)

Input (non-polling)

40027/17

17

04-Outlet Temp

localsuptemp_1
7

AV:174

data
float

174

nvoEcsSupTmp17

inc count (9)

Output (non-polled)

30002/17

17

05-FBk Sensor
Temp

localrettemp_17

AV:175

data
float

175

nvoEcsRetTmp17

inc count (9)

Output (non-polled)

30170/17

17

06-Over Temp
Alarm

unitstat_17

AV:176

data
float

176

nvoEcsStat17

inc count (9)

Output (non-polled)

30075/17

17

07-Flow Rate

flowrate_17

AV:177

data
float

177

nvoEcsFlow17

inc count (9)

Output (non-polled)

30171/17

E Valve Addr 18

18

01-Cntl Output
Signal

boilerstate_18

AV:181

data
float

181

nvoEcsState18

inc count (9)

Output (non-polled)

18004/18

18

02-Setpoint

effectsetpt_18

AV:182

data
float

182

nvoEcsSetpt18

inc count (9)

Output (non-polled)

18006/18

18

03-RmSetpt

rmsetpt_18

AV:183

data
float

183

nviEcsSetptRq18

inc count (9)

Input (non-polling)

40027/18

18

04-Outlet Temp

localsuptemp_1
8

AV:184

data
float

184

nvoEcsSupTmp18

inc count (9)

Output (non-polled)

18002/18

18

05-FBk Sensor
Temp

localrettemp_18

AV:185

data
float

185

nvoEcsRetTmp18

inc count (9)

Output (non-polled)

18290/18

18

06-Over Temp
Alarm

unitstat_18

AV:186

data
float

186

nvoEcsStat18

inc count (9)

Output (non-polled)

18075/18

18

07-Flow Rate

flowrate_18

AV:187

data
float

187

nvoEcsFlow18

inc count (9)

Output (non-polled)

18291/18

E Valve Addr 19

19

01-Cntl Output
Signal

boilerstate_19

AV:191

data
float

191

nvoEcsState19

inc count (9)

Output (non-polled)

30004/19

19

02-Setpoint

effectsetpt_19

AV:192

data
float

192

nvoEcsSetpt19

inc count (9)

Output (non-polled)

30006/19

19

03-RmSetpt

rmsetpt_19

AV:193

data
float

193

nviEcsSetptRq19

inc count (9)

Input (non-polling)

40027/19

Advertising