CHAPTER 8:

Configuration Information

8.1 Default ProtoNode Modbus RTU COM Settings for AERCO

Controllers

Table 8-1: Default Serial Port Settings

Serial Port Setting

ACS, BMS II,

BMS

ECS/SP

BCM

(Modulex)

C-More

Baud Rate

9600

9600

9600

9600

Data Bits

8

8

8

8

Stop Bits

1

1

1

1

Parity

None

None

None

None

Table 8-2: Default Address Settings

Configuration

Controllers

Name

Modbus Default

Address

4 C-More Controllers

up to

12 C-More Controllers

&

1 ACS/BMS II/BMS

C-more 1

Blr Addr 1

1

C-more 2

Blr Addr 2

2

C-more 3

Blr Addr 3

3

C-more 4

Blr Addr 4

4

C-more 5

Blr Addr 5

5

C-more 6

Blr Addr 6

6

C-more 7

Blr Addr 7

7

C-more 8

Blr Addr 8

8

C-more 9

Blr Addr 9

9

C-more 10

Blr Addr 10

10

C-more 11

Blr Addr 11

11

C-more 12

Blr Addr 12

12

ACS /BMS II

BMS Addr 128

128

4 Modulex Controllers

&

1 ACS/BMS II/BMS

Modulex 1

Mlx Addr 1

1

Modulex 2

Mlx Addr 2

2

Modulex 3

Mlx Addr 3

3

Modulex 4

Mlx Addr 4

4

ACS /BMS II

BMA Addr 128

128

4 ECS/SP

ECS 1

E Value Addr 29

29

ECS 2

E Value Addr 30

30

ECS 3

E Value Addr 31

31

ECS 4

E Value Addr 32

32

For Profiles defined in Appendix C, the ECS/SP Modbus default point addresses are defined
below.