Table C-1: Four C-Mores and One ACS/BMS II/BMS
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/
Unit Addr.
128
20-Net Blr 3 Status
blr11stat_5
AV:8
data float
60
nvoNetBlr3Stat
inc count (9) Output (non-polled)
30028/128
128
21-Net Blr 4 Status
blr12stat_5
AV:9
data float
61
nvoNetBlr4Stat
inc count (9) Output (non-polled)
30029/128
128
22-Return Temp
localrettemp_5
AV:173
data float
173 nvoLocRetTmp
inc count (9) Output (non-polled)
30004/128