Table F-2: BMM Fault Code Table (Cont.)

Code Description

Effect

Correction

Reset

24

Fan speed out of
control: It doesn't
reach pre-purge
speed within 30
seconds.

Ignition retry after
60 second delay
and failure
remains until we
have a successful
burner operation.

Check fan wiring.

AUTOMATIC/
MANUAL

26

Fan speed out of
control: It doesn't
stop within 30
seconds after
turned OFF.

Ignition is
inhibited.

Check fan wiring.

AUTOMATIC

27

Air flow failure
during ignition.

Restart pre-purge
timer. The failure
remains until we
have a successful
burner operation.

Check fan and wiring.
Check air proving switch and
wiring.

AUTOMATIC

28

Flue/Chimney
Obstruction

Ignition is
inhibited.

Check flue/chimney

29

Water inside the
combustion
chamber.

Ignition is
inhibited.

Check for water in the
exhaust manifold

30

Settings Corrupted

Ignition is
inhibited. Pump
runs for 5 min at
max speed.

Re-program the settings.
Contact Factory

MANUAL - cycle the
power or send reset
message.

32

Line voltage too
low. (<96 VAC)

Wait for proper
line voltage.
(>102 VAC)

Check input voltage else try
another BMM.

AUTOMATIC

40

Low Water Flow.
Low water flow
switch activated.

Burners turned
OFF.

Check water flow or check
switch.

AUTOMATIC