Aerco protonode gateway, User manual, Table c-4: four modulex and one acs/bms ii – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 88

Advertising
background image

AERCO ProtoNode Gateway

User Manual

Page 88 of 126

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0080_0H

11/06/2014

Ph.: 800-526-0288

GF-129

Table C-4: Four Modulex and One ACS/BMS II

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2

Type

N2

ID

Lon SNVT

NAME

Lon SNVT

Lon Direction

ModBus/Unit

Address

4

05-Mod Lev In

boilerload_4

AV:43

data
float

179

nvoMlxLoad4

inc count (9)

Output (non-polled)

41201/4

4

06-Flow Sens
Temp

localsuptemp_4

AV:44

data
float

180

nvoMlxSupTmp4

inc count (9)

Output (non-polled)

41003/4

4

07-Display Code

dispcode_4

AV:45

data
float

181

nvoMlxDispCode4

inc count (9)

Output (non-polled)

30001/4

4

11-Error Code

errcode_4

AV:10

data
float

182

nvoMlxErrCode4

51

Output (non-polled)

40001/4

4

08-Unit Status

unitstat_4

AV:46

data
float

183

nvoMlxStat4

inc count (9)

Output (non-polled)

30002/4

4

09-Ret Flow Temp

returntemp_4

AV:11

data
float

184

nvoMlxRetTmp4

inc count (9)

Output (non-polled)

41004/4