Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2 Type

N2

ID

Lon SNVT

NAME

Lon

SNVT

Lon Direction

ModBus
Address

Master Addr 247

Master Control Values

247

Write Cntrl Val to

BST/WHM

SMD_BAS_IP_Ctrl_[1]

write "1" to

send Value to

WHM

AV:51

Data Float

2

nvoCtrl_2

inc count (9)

Input/Output

40051

247

BST/WHM Timeout

SMD_BAS_IP_Ctrl_[3]

**Read

Only**,

0=WHM

Present,

1=WHM

Absent

AV:53

Data Float

4

nvoCtrl_4

inc count (9)

Input/Output

40053

Read Master Operating Values

247

Mode

SMD_BAS_IP_OpVal_[0]

AV:100

Data Float

6

nvoOpVal_1

inc count (9)

Output (non-polled)

30100

247

Setpoint

SMD_BAS_IP_OpVal_[1]

AV:101

Data Float

7

nvoOpVal_2

inc count (9)

Output (non-polled)

30101

247

Setback Setpt

SMD_BAS_IP_OpVal_[2]

AV:102

Data Float

8

nvoOpVal_3

inc count (9)

Output (non-polled)

30102

247

Setback Start

SMD_BAS_IP_OpVal_[3]

AV:103

Data Float

9

nvoOpVal_4

inc count (9)

Output (non-polled)

30103

247

Setback End

SMD_BAS_IP_OpVal_[4]

AV:104

Data Float

10

nvoOpVal_5

inc count (9)

Output (non-polled)

30104

247

Auto Master

SMD_BAS_IP_OpVal_[5]

AV:105

Data Float

11

nvoOpVal_6

inc count (9)

Output (non-polled)

30105

247

Avg Outlet Temp

SMD_BAS_IP_OpVal_[6]

AV:106

Data Float

12

nvoOpVal_7

inc count (9)

Output (non-polled)

30106

247

Units Active

SMD_BAS_IP_OpVal_[7]

AV:107

Data Float

13

nvoOpVal_8

inc count (9)

Output (non-polled)

30107

247

Units Faulted

SMD_BAS_IP_OpVal_[8]

AV:108

Data Float

14

nvoOpVal_9

inc count (9)

Output (non-polled)

30108

247

Master Addr

SMD_BAS_IP_OpVal_[9]

AV:109

Data Float

15

nvoOpVal_10

inc count (9)

Output (non-polled)

30109

247

Header Temp

SMD_BAS_IP_OpVal_[10]

AV:110

Data Float

16

nvoOpVal_11

inc count (9)

Output (non-polled)

30110

247

Outdoor Temp

SMD_BAS_IP_OpVal_[11]

AV:111

Data Float

17

nvoOpVal_12

inc count (9)

Output (non-polled)

30111

247

Percent Output

SMD_BAS_IP_OpVal_[12]

AV:112

Data Float

18

nvoOpVal_13

inc count (9)

Output (non-polled)

30112

247

Number of Units

Firing

SMD_BAS_IP_OpVal_[13]

AV:113

Data Float

19

nvoOpVal_14

inc count (9)

Output (non-polled)

30113

247

Master Active

Setpoint

SMD_BAS_IP_OpVal_[14]

AV:114

Data Float

20

nvoOpVal_15

inc count (9)

Output (non-polled)

30114

Advertising