Table 1 — physical data (cont) – Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EY024-048 User Manual

Page 11

Advertising
background image

Table 1 — Physical Data (cont)

UNIT 48EJ,EK,EW,EY

038D/E

044D/E

048D/E

NOMINAL CAPACITY (tons)

35

40

45

OPERATING WEIGHT (lb)*

Unit

Al/Al† (Lo Heat/Hi Heat)

4442/4602

4668/4828

4955/5115

Al/Cu† (Lo Heat/Hi Heat)

4727/4887

4953/5113

5335/5495

Roof Curb (14-in. curb)

410

410

410

COMPRESSOR

Type

Ckt 1

06D537

06EA250

06EA265

Ckt 2

06D537

06EA250

06EA250

Number of Refrigerant Circuits

2

2

2

Oil (oz) (Ckt 1, Ckt 2)

115 ea.

224 ea.

304, 224

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)

Circuit 1**

34-0

35-0

41-0

Circuit 2

34-0

35-0

41-0

CONDENSER COIL

Cross-Hatched

3

8

Љ

Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins

Quantity

2

2

1

1

Rows...Fins/in.

3...15

3...15

4...15

3...15

Total Face Area (sq ft)

58.3

58.3

66.7

CONDENSER FAN

Propeller Type

Nominal Cfm

27,064

27,064

27,064

Quantity...Diameter (in.)

4...30

4...30

4...30

Motor Hp (1075 Rpm)

1

1

1

EVAPORATOR COIL

Cross-Hatched

3

8

Љ

Copper Tubes, Aluminum Plate Fins, Intertwined Circuits

Rows...Fins/in.

3...15

3...15

4...15

Total Face Area (sq ft)

34.7

34.7

34.7

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

2...20x15

2...20x15

2...20x15

Type Drive

Belt

Belt

Belt

Nominal Cfm

14,000

16,000

18,000

Motor Hp

10

15††

20

15

20††

25

20

25††

30

Motor Frame Size (Standard)

S215T

D254T

S256T

D254T

S256T

S284T

S256T

S284T

S286T

(High Efficiency)

S215T

S254T

S256T

S254T

S256T

S284T

S256T

S284T

S286T

Motor Bearing Type

Ball

Ball

Ball

Maximum Allowable Rpm

1200

1200

1200

Motor Pulley Pitch Diameter

6.1

5.3

5.7

5.3

5.7

7.5

6.3

5.9

7.5

Nominal Motor Shaft Diameter (in.)

1

3

8

1

5

8

1

5

8

1

5

8

1

5

8

1

7

8

1

5

8

1

7

8

1

7

8

Fan Pulley Pitch Diameter (in.)

13.7

9.5

9.5

9.5

9.5

11.1

11.1

12.5

11.1

Nominal Fan Shaft Diameter (in.)

1

15

16

1

15

16

1

15

16

Belt, Quantity...Type
Belt, Length (in.)

1...5VX650

65

2...5VX530

53

2...5VX550

55

2...5VX530

53

2...5VX550

55

2...5VX590

59

2...5VX570

57

2...5VX630

63

2...5VX610

59

Pulley Center Line Distance (in.)

15.6-18.4

15.0-17.9

15.0-17.9

14.6-17.6

15.0-17.9

14.6-17.6

Factory Speed Setting (rpm)

779

976

1050

976

1050

1182

993

1134

1182

FURNACE SECTION

Rollout Switch Cutout Temp (F)

225

225

225

Burner Orifice Diameter

(in. ...drill size)

Natural Gas

Std

.120...31

.120...31

.120...31

Liquid Propane

Alt

.096...41

.096...41

.096...41

Thermostat Heat Anticipator

Setting (amps)

Stage 1

0.1

0.1

0.1

Stage 2

0.1

0.1

0.1

Gas Input (Btuh)

Stage 1

Low

300,000

300,000

300,000

High

600,000

600,000

600,000

Stage 2

Low

400,000

400,000

400,000

High

800,000

800,000

800,000

Efficiency (Steady State) (%)

82

82

82

Temperature Rise Range

10-40/30-60

10-40/30-60

10-40/30-60

Manifold Pressure (in. wg)

Natural Gas

Std

3.5

3.5

3.5

Liquid Propane

Alt

3.5

3.5

3.5

Gas Valve Quantity

2

2

2

Field Gas Connection Size (in.-FPT)

1.5

1.5

1.5

HIGH-PRESSURE SWITCH (psig)

Cutout

426

426

426

Reset (Auto.)

320

320

320

LOW-PRESSURE SWITCH (psig)

Cutout

7

7

7

Reset (Auto.)

22

22

22

OUTDOOR-AIR FILTERS

8...16 × 25

Quantity...Size (in.)

4...20 × 25

RETURN-AIR FILTERS

Quantity...Size (in.)

10...20x24x2

10...20x24x2

10...20x24x2

POWER EXHAUST

Direct Drive, 3-Speed, Single-Phase motor (Factory-Wired for High Speed) and Forward Curved Fan

Motor, Quantity...Hp

4...1

4...1

4...1

Fan, Diameter... Width (in.)

11...10

11...10

11...10

LEGEND

Al

Aluminum

Cu

Copper

*Weight of unit does not include variable frequency drive (VFD) barometric relief, or power

exhaust. If a VFD is installed, add the VFD weight in the table at right.

†Evaporator coil fin material/condenser coil fin material.

**Sizes 024-034: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper

portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units
have intertwined evaporator coils.

††Motor and drive shown will deliver approximately 2.5 in. wg net external static. See

Table 2 for more information.

Rollout switch is manual reset.

NOTE: High heat is for 48EJ,EW only.

VFD
(Hp)

VFD WEIGHTS (lb)

208/230 v

460 v

575 v

5

20

22

60

7.5

51

37

64

10

51

61

64

15

61

63

109

20

63

111

109

25

105

112

174

30

172

118

180

11

Advertising