MORNING WARM-UP (VAV Only) (Stand-Alone Opera-
tion) — When the unit operates in stand-alone mode, morn-
ing warm-up occurs when the unit is energized in Occupied
mode and return-air temperature (RAT) is below 68 F. Warm-up
will not terminate until the RAT reaches 68 F. The heat in-
terlock relay output is energized during morning warm-up.
(A field-installed 24-vdc heat interlock relay is required.) The
output will be energized until the morning warm-up cycle is
complete. Refer to Fig. 42 for heat interlock relay wiring.

SPACE TEMPERATURE RESET SENSOR (VAV Only) —
An accessory space temperature sensor wired to terminals
T1 and T2 on the control module is required. Space tem-
perature reset is used to reset the supply-air temperature set
point of a VAV system higher, as the space temperature falls
below the Occupied Cool set point. As the space tempera-
ture falls below the Occupied Cool set point, the supply-air
temperature will be reset upward as a function of the reset
ratio. (Default is 3.) Reset ratio is expressed in degrees change

in supply-air temperature per degree of space temperature
change. A reset limit will exist which will limit the maxi-
mum number of degrees the supply-air temperature may be
raised. (Default is 10 F.) Both the reset ratio and the reset
limit are user definable. The sequence of operation is as
follows:
1. The on/off status of the unit supply fan is determined.
2. If the fan is ‘‘on,’’ the sequence will check if the system

is occupied.

3. If the system is occupied, the sequence will determine if

the reset option is enabled.

4. If the reset option is enabled, the sequence will read the

space temperature and compare it to the Occupied Cool
set point. If the temperature is below the Occupied Cool
set point, the algorithm will compute the reset value and
compare this value against the reset limit. If it is greater
than the reset limit, the sequence will use the reset limit
as the reset value.

BASE MODULE

CONTROL BOARD

T

30

T29

T

28

COM

COM

B

TRAN2

SECONDARY

24 VOLT

CB4

3.2 AMPS

INDOOR FAN RELAY

HIR

FIELD

INSTALLED

(HN61KK040)

(24V, 9.5VA)

LEGEND

CB

Circuit Breaker

COM

Common

HIR

Heat Interlock Relay

T

Terminal

TRAN — Transformer

Fig. 42 — Heat Interlock Relay Wiring

4-20 mA

INPUT

FIELD

SUPPLIED

INPUT DEVICE

BASE MODULE

CONTROL BOARD

(+) T11

(–) T12

LEGEND

T — Terminal

NOTE: The 4 to 20 mA input is a field-supplied non-
Carrier EMS (Energy Management System) device.

Fig. 43 — Space Temperature Reset Wiring

mA INPUT

DEG. F RESET

4

0.00

5

1.25

6

2.50

7

3.75

8

5.00

9

6.25

10

7.50

11

8.75

12

10.00

13

11.25

14

12.50

15

13.75

16

15.00

17

16.25

18

17.50

19

18.75

20

20.00