The alarm codes for the IGC control board are shown in

Table 22.

Table 22 — IGC Control Board LED Alarms

INDICATION

ERROR MODE

ON

Normal Operation

OFF

Hardware Failure

1 FLASH

Fan ON/OFF Delay Modified

2 FLASHES

Limit Switch Fault

3 FLASHES

Flame Sense Fault

4 FLASHES

4 Consecutive Limit Switch Faults

5 FLASHES

Ignition Lockout Fault

6 FLASHES

Induced Draft Motor Fault

7 FLASHES

Rollout Switch Fault

8 FLASHES

Internal Control Fault

Diagnostic LEDs —

There are 3 LEDs (red, yellow,

and green) on the lower right hand side of the control board.
The red light is used to check unit operation and alarms. A
constant pulse is normal unit operation. A series of quick
blinks indicates an alarm. Refer to Table 23 below for a de-
scription of alarms. The yellow LED blinks during transmis-
sion with the CCN (Carrier Comfort Network). The green
LED blinks during transmission with the expansion board.

Table 23 — Control Board LED Alarms

LED Blinks

Error Code

Description

Troubleshooting Comments

1

Normal Operation

The expansion board and control board flash the red LED in one-second
intervals when the board is operating properly.

2

HF-13

Compressor 1 Safety

The high or low pressure safety switch for compressor no. 1 has opened for
3 seconds. The error will be cleared and compressor no. 1 will be allowed
to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 min-
utes, compressor no. 1 will be locked out until the control board has been
manually reset.

3

HF-14

Compressor 2 Safety

The high or low pressure safety switch for compressor no. 2 has opened for
3 seconds. The error will be cleared and compressor no. 2 will be allowed
to turn on in 15 minutes. If the safeties have been tripped 3 times in 90 min-
utes, compressor no. 2 will be locked out until the control board has been
manually reset.

4

HF-15

Thermostat Failure

The thermostat is calling for both heating and cooling at the same time. The
unit will operate on a first call basis and will automatically reset.

5

HF-05

SAT Thermistor Failure

The supply-air temperature (SAT) sensor has failed. First check for wiring
errors, then replace sensor.

6

HF-06

OAT Thermistor Failure

The outside air temperature (OAT) sensor has failed. First check for wiring
errors, then replace sensor.

7

HF-03

Space Temp. Sen. Failure

The space temperature sensor has failed. First check for wiring errors, then
replace sensor.

8

HF-12

RAT Thermistor Failure

The return-air temperature (RAT) sensor has failed. Ensure that the unit is
a VAV unit. If NOT a VAV unit set DIP switch position 1 to the closed position
and reset power. Then check for wiring errors. Finally, replace sensor.

9

SE-05

Loss of Communications
with Expansion Board

Communications between the expansion board and the control board have
been interrupted. Ensure that an expansion board is installed and wired us-
ing the wire harness supplied with the expansion module. If an expansion
board is not used ensure that DIP switch position 3 is in the closed position,
and reset power.

10

HF-16

Control Board Failure

Generated when hardware has failed on control board. Replace the control
board.

11

HF-17

Expansion Board Failure

Generated when hardware has failed on the expansion board. Replace the
expansion board.

DIP

Dual In-Line Package

VAV — Variable Air Volume