Table 4 — Electrical Data (cont)

UNIT

SIZE

48E

NOMINAL
VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER SUPPLY

No. 1

No. 2

Min

Max

RLA LRA RLA

LRA

Qty Hp

FLA

(ea)

Hp

FLA

FLA LRA

FLA

MCA

MOCP*

034

208/230

187

254

57.1

266

57.1

266

2

1

5.3

10

30.8/
28.0

0.96

169.9/167.1 225/200

23.6

41.6

0.96

193.5/190.7 250/225

15

46.2/
42.0

0.96

185.3/181.1 225/225

23.6

41.6

0.96

208.9/204.7 250/250

20

59.4/
54.0

0.96

198.5/193.1 250/250

23.6

41.6

0.96

222.1/216.7 275/250

460

414

508

25.6

120

25.6

120

2

1

2.7

10

14.0

0.50

77.0

100

12.6

23.6

0.50

89.6

110

15

21.0

0.50

84.0

100

12.6

23.6

0.50

96.6

110

20

27.0

0.50

90.0

110

12.6

23.6

0.50

102.6

125

575

518

632

20.5

96

20.5

96

2

1

2.4

10

11.0

0.50

61.9

80

12.6

23.6

0.50

74.5

90

15

17.0

0.50

67.9

80

12.6

23.6

0.50

80.5

100

20

22.0

0.50

72.9

90

12.6

23.6

0.50

85.5

100

038

208/230

187

254

57.1

266

57.1

266

4

1

5.3

10

30.8/
28.0

0.96

180.5/177.7 225/225

23.6

41.6

0.96

204.1/201.3 250/250

15

46.2/
42.0

0.96

195.9/191.7 250/225

23.6

41.6

0.96

219.5/215.3 275/250

20

59.4/
54.0

0.96

209.1/203.7 250/250

23.6

41.6

0.96

232.7/227.3 275/275

460

414

508

25.6

120

25.6

120

4

1

2.7

10

14.0

0.50

82.4

100

12.6

23.6

0.50

95.0

110

15

21.0

0.50

89.4

110

12.6

23.6

0.50

102.0

125

20

27.0

0.50

95.4

110

12.6

23.6

0.50

108.0

125

575

518

632

20.5

96

20.5

96

4

1

2.4

10

11.0

0.50

66.7

80

12.6

23.6

0.50

79.3

90

15

17.0

0.50

72.7

90

12.6

23.6

0.50

85.3

100

20

22.0

0.50

77.7

90

12.6

23.6

0.50

90.3

110

LEGEND

or

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more
than

2%,

contact

your

local

electric

utility

company

immediately.

19